12 Freedom SW 230V Installation Guide
Planning Preparations
For dual input, the wire may be red or black; consult the
documentation provided with the AC source (utility or generator).
Size of AC Output Wiring Wire size must be coordinated with
the current the wiring will carry. This current may be determined by
the 15-amp (Freedom SW 3524-230) and 11-amp (Freedom SW
2524-230) maximum inverter current, or by the bypass current,
which is determined by the overcurrent protection provided ahead
of the Freedom SW 230V.
Size of Wiring Downstream of the AC Output Breaker The
wiring used between the AC output breaker and your loads must be
sized in accordance with the rating of the output breaker.
Table 1 AC Wire Size In and Out of the Inverter/Chargers
MODELS Freedom SW 230V
Breaker Size Used 30 amps
Wire Size 4 mm
2
(minimum)
Color Coding L: brown, black, or grey
N: blue
G: green with yellow stripe
Freedom SW 3K2K 230V InvChg Install Guide.book Page 12 Friday, June 20, 2014 9:11 AM