MP2000 AIR CONDITIONERS
Software per condizionatori d'aria EPROM CZX....
Software for air conditioners
PARAMETRI TEMPORIZZAZIONI
TIMING PARAMETERS
Premere per 4 secondi
HOME
1
PRG
3
Press for 4 seconds
quindi inserire Password
than digit Password
ON DISPLAY TIPO DI SET
SET TYPE
DEFAULT RANGE SYMBOL
Time delay switching main fan on ritardo attivazione ventilatore principale
main fan on delay
2s 0÷600 s
Time delay switching main fan off ritardo disattivazione ventilatore principale
main fan off delay
10s 0÷600 s
Float. valve running time tempo funzionamento valvola 3 punti
floating valve running time
150s 0÷600 s
Alarm delay time low pressure ritardo allarme bassa pressione
low pressure alarm delay
300s 0÷600 s
Alarm delay time air flow ritardo allarme flusso aria
air flow alarm delay
15s 0÷600 s
Alarm delay time oil diff. ritardo allarme pressione differenziale olio
differential oil pressure alarm delay
120s 0÷600 s
Hi/lo temp. alarm delay time ritardo allarme alta/bassa temperatura
low/high temperature alarm delay
300s 0÷9999 s
Hi/lo humidity alarm delay time ritardo allarme alta/bassa umidità
low/high umidity alarm delay
1800s 0÷9999 s
Minimum compressor off time tempo minimo di fermo compressore
minimum off time compressor
120s 0÷600 s
Minimum compressor on time tempo minimo di funz. compressore
minimum on time compressor
60s 0÷600 s
Delay between starts same comp. ritardo minimo tra gli avviamenti dello
minimum delay between starts
stesso compressore
of the same compressor
180s 0÷600 s
Delay between starts diff. comp. ritardo minimo tra lavviamento di un
minimum delay between start of one
compressore ed il successivo
compressor and the next one
. 10s 0÷600 s
Delay between starts two unload. ritardo minimo per passaggio da 100%
minimum delay to change from 100%
a 50% capacità e viceversa.
to 50% capacity and viceversa.
(parzializzazioni o doppia velocità)
(unloading or double speed)
10s 0÷600 s
Delay between stars diff. heat. ritardo minimo tra lattivazione di uno
minimum delay between one heating
stadio di riscaldamento e laltro.
stage activation and the next one
5s 0÷600 s
INIZIALIZZAZIONE UNITA
UNIT INITIALIZATION
Premere per 4 secondi
HOME
1
PRG
3
Press for 4 seconds
quindi inserire Password
than digit Password
ON DISPLAY TIPO DI SET
SET TYPE
DEFAULT RANGE SYMBOL
Do you want insert manufacturer vuoi inserire i parametri manufacturer?
do you want insert manufacturer
parameters?
parameters?
ripristino set di base
reset to default set
N N - Y
SET PROGRAMMABILI
PROGRAM SETS
Premere
PRG
3
Press
quindi inserire Password
than digit Password
ON DISPLAY TIPO DI SET
SET TYPE
DEFAULT RANGE SYMBOL
Temperature set point limits limiti set point temperatura
temperature set point limits
Minimum minimo
minimum
10°C0÷50 °C
Maximum massimo
maximum
30°C0÷50 °C
Humiditiy set point limits limiti set point umidità
humidity set point limits
Minimum minimo
minimum
35%rH 30÷90 %rH
Maximum massimo
maximum
80%rH 30÷90 %rH
Interg. humidifier production produzione vapore umidificatore
steam humidifier production
3Kg/h 1,4÷5 Kg/h
Local off switch enabled abilitazione tasto ON/OFF locale
local ON/OFF switch enabled
Y N - Y
Reduce humid. in cool position riduzione umidif. con richiesta freddo
humidif. reduction with cool request
Y N - Y
Control condensing pressure pressione controllo condensazione
control condensing pressure
Setpoint valore segnale proporzionale minimo
proportional signal min. value
1400kPa 0÷3000 kPa zPs
Differential valore segnale proporzionale massimo
proportional signal max. value
300kPa 0÷1000 kPa zP
Control condensing pressure pressione controllo condensazione
control condensing pressure
(compr. off) (compressore off)
(compressor off)
On (max V) vent. condensatore ON con compr. OFF
cond. fan ON with compr. OFF
2200kPa 0÷3000 kPa zON
Off (min V) vent. condensatore OFF con compr. OFF
cond. fan OFF with compr.OFF
2000kPa 0÷3000 kPa zOFF
Condensing output min value valore mimino uscita condensazione
condensing output min value
3V 0÷5 V zPmin
Condensing output max value valore massimo uscita condensazione
condensing output max value
10V 5÷10 V zPmax
Maximum pressure value massimo valore di pressione
max pressure value
2500kPa 0÷4000 kPa zH.Alarm
Max compensation setpoint massimo valore di compensazione
max compensation value
5°C ±20 °C
Reaction time tempo di reazione compensazione
compensation reaction time
5min 2÷30 min
Offset room temp. high preal. preallame alta temperatura ambiente
high room temperature prealarm
4,5°C (offset) 2÷20 °C xH.prealarm
Offset room temp. low alarm allarme bassa temperatura ambiente
low room temperature alarm
4,5°C (offset) 2÷20 °C xL.alarm
Offset room temp. high alarm allarme alta temperatura ambiente
high room temperature alarm
5,5°C (offset) 2÷20 °C xH.alarm
Offset room humidity low alarm allarme bassa umidità ambiente
low room humidity alarm
14%rH (offset) 5÷50 %rH yL.alarm
Offset room humidity high alarm allarme alta umidità ambiente
high room humidity alarm
14%rH (offset) 5÷50 %rH yH.alarm
Limit thermostat enable abilitazione termostato limite uscita aria
outlet air limit thermostat enabling
N N - Y
Threshold limit cooling soglia limitazione raffreddamento
cooling limit threshold
14°C0÷20°C