99
RC GROUP - 149_ItEn.0102
MP2000 AIR CONDITIONERS
Software per condizionatori d'aria a pompa di calore e Roof Top • EPROM CPX....
• Software for heat pump air conditioners and Roof Top
CONFIGURAZIONE UNITA’
UNIT CONFIGURATION
Premere per 4 secondi
HOME
1
PRG
3
Press for 4 seconds
quindi inserire Password
than digit Password
ON DISPLAY TIPO DI SET
SET TYPE
DEFAULT RANGE SYMBOL
Clock board scheda orologio
clock board
N N - Y —
Supervisor code codice supervisione
supervisor code
0 00 ÷ 99 —
Supervisor mode modo supervisore
supervisor mode
R R - W —
Probe selction selezione sonda
probe selection
Supply air temp. temperatura mandata aria
supply air temperature
N N - Y —
Outl. water temp. uscita acqua condensatore
outlet condenser water
N N - Y —
Ext. air temp. temperatura aria esterna
external air temperature
N N - Y —
Room humidity umidità ambiente
room humidity
N N - Y —
Integr. humidif. umidificatore integrato (*)
integrated humidifier (*)
N N - Y —
High pressure probe present presenza sonda di alta pressione
high pressure probe present
N N - Y —
Min. scale scala minima pressione
min pressure scale
0 kPa ±500 kPa —
Max. scale scala massima pressione
max pressure scale
3000 kPa 0÷5000 kPa —
Low pressure probe min. scale scala minima sonda di bassa pressione
low pressure probe min. scale
0 kPa 0÷500 kPa —
Low pressure probe max. scale scala massima sonda di bassa pressione
low pressure probe max. scale
1500 kPa 0÷1500 kPa —
Analog input 7 board 1 used like ingr. analogico 7 board 1 usato come (*)
analog input 7 boad 1 used like (*)
not used not used —
voltage line
line current
ext. compens.
(*) con “Integr. humidif. Y” è utilizzato in
(*) with “Integr. humidif. Y” it is automatically
automatico per corrente umidificatore e
used for humidifier current measurement
questo set non viene visualizzato.
and this set is not displayed
Analog input 7 board 2 used like ingr. analogico 7 board 2 usato come
analog input 7 boad 2 used like
not used not used —
voltage line
line current
ext. compens.
Analog input 8 board 2 used like ingr.analogico 8 board 2 usato come
analog input 8 board 2 used like
not used not used —
voltage line
line current
ext. compens.
Voltage line max scale scala massima tensione linea
max voltage line scale
600 V 0÷700 V —
Line current max scale scala massima corrente linea
max line current scale
100 A 0÷700 A —
Configuration configurazione unità
unit configuration
2 compr. - 2 circ. - 2 board ——
2 compr. - 1 circ. - 2 board ——
2 compr. - 1 circ. - 1 board ——
1 compr. - 2 board ——
1 compr. - 1 board ——
Enable heater abilitazione riscaldamento
enable heater
N Y - N —
Condenser type tipo di condensatore
condenser type
AIR AIR - WATER —
Unloader comp. parzializzazione compressore
unloader compressor
N N - Y —
En. double speed compressore doppia velocità
double speed compressor
N N - Y —
Analog out.1 board 1 uscita analogica xY0 board 1
analog output xY0 board 1
cooling valve cooling valve xY0
heating valve
not used
cool valve +dehumid
Analog out.1 board 2 uscita analogica xY0 board 2
analog output xY0 board 2
cooling valve cooling valve xY0
heating valve
not used
cool valve +dehumid