Ingersoll-Rand X41 Air Compressor User Manual


 
Compressor
#1
IR-PCB
DRIP LEG
PRESSURE TRANSDUCER
RECEIVER
Compressor
#3
IR-PCB
Compressor
#4
IR-PCB
Compressor
#2
IR-PCB
PRESSURE TRANSDUCER CABLE
2 Conductor Cable, 18 Gauge Stranded
Earth Shielded
No Greater Than 330FT (100M)
24VDC Control Voltage
X4I X05 CONNECTOR PT CONNECTOR
25 +VDC Pin #3
26 Signal Pin #1
Reference X4I Operations Manual for Pressure
Sensor Connection Details
COMPRESSOR CONTROL CABLE
7 Conductor Cable, 18 Gauge, Stranded, Earth Shielded
OR
Single Conductor Wire, 18 Gauge Stranded, Quantity (7)
In Grounded Conduit
No Greater Than 330FT (100M)
24VAC Control Voltage
Compressor #4 Control Cable
Compressor #3 Control Cable
Compressor #2 Control Cable
Compressor #1 Control Cable
Pressure Transducer Cable
Compressor #2 Control Cable
X4I X02 CONNECTOR IR-PCB CONNECTOR
V3 V1
7 1
8 2
9 3
10 4
11 5
12 6
Compressor #3 Control Cable
X4I X03 CONNECTOR IR-PCB CONNECTOR
V3 V1
13 1
14 2
15 3
16 4
17 5
18 6
Compressor #4 Control Cable
X4I X04 CONNECTOR IR-PCB CONNECTOR
V4 V1
19 1
20 2
21 3
22 4
23 5
24 6
Compressor #1 Control Cable
X4I X01 CONNECTOR IR-PCB CONNECTOR
V1 V1
1 1
2 2
3 3
4 4
5 5
6 6
Reference X4I Compressor
Interconnect and Application Guide
For Connections Between The
Compressor And The IR-PCB
SPECIFICATIONS
Dimensions 11.45” x 9.45” x 6.0”
291mm x 241mm x 152mm
Weight 14lb (6.4kg)
Mounting Wall, 4 x screw fixings
Enclosure IP65, NEMA 4
Supply 230Vac +/- 10%, 50 Hz
115Vac +/- 10%, 60 Hz
Power 50VA
Temperature 32°F to 115°F
(0°C to 46°C)
Humidity 0% to 95% RH
(non-condensing)
Ingersoll Rand Automation
Model X4I
Supply Voltage Cable
Local Disconnect (Breaker) Box
Fused for 50VA
Power Cable
3 conductor (L, N, E)
(Sized in accordance with local
electrical and safety regulations).
On/Off
Switch
X4I Overview Page 14