Ingersoll-Rand X41 Air Compressor User Manual


 
X4I Interconnect To Ingersoll Rand Intellisys Redeye Controlled Compressors
Refer to the X4I Overview Drawing for the X4I Compressor 2 through 4 X01 to IR-PCB terminal connections
For Redeye Intellisys Controlled Machines:
The ‘MASTER CONTROL’ setting of the Intellisys controller must be set to ‘ON’
The 'SEQUENCER' setting of the Intellisys controller must be set to 'ON'.
Auto Restart must be turned 'ON’ to allow the machines to stop in Auto restart when unloaded by the X4I.
The Intellisys must be run in the Online/Offline regulation mode. Do not use Modulation or ACS.
Check the Intellisys software revision level. Always update to the latest revision prior to operation.
For DSA Redeye Controllers, the 'SEQUENCER Option’ must be purchased. installed and then turned on.
CCN: 39225099
For ESA Redeye Intellisys Controllers, the SI1 interface (CCN: 42425710) must be used to allow the Redeye to be controlled by the X4I
For Sierra Redeye Intellisys Controllers, the SI1 interface (CCN: 42425710) must be used to allow the Redeye Controller to be sequenced/controlled
by the X4I
Drawing Notes For Redeye Intellisys Controlled Machines:
Note: For Star Delta starter wiring the X4I Run signal should be connected directly to the 1M coil.
Note: For Full voltage wiring the 1S (1Sb) interlock will not be used. The X4I Run signal can be connected directly to the Intellisys BTS1-28 terminal.
Guidance only; connections may differ with date, model, type, variant, special, custom or concession builds. This information is intended to be
used in conjunction with the compressor’s original control circuit diagram.
X4I Interconnect To Ingersoll Rand Intellisys Redeye Controlled Compressors Page 22