Ingersoll-Rand X41 Air Compressor User Manual


 
X4I Interconnect To Ingersoll Rand Intellisys S3
Refer to the X4I Overview Drawing for the X4I Compressor 2 through 4 X01 to IR-PCB terminal connections
For All S3 Intellisys Controlled Machines:
The 'REMOTE CONTROL' setting “RC” of the Intellisys controller must be set to 'ON'.
Auto Restart must be turned 'ON’ to allow the machines to stop in Auto restart when unloaded by the X4I.
The Intellisys must be run in the Online/Offline regulation mode. Do not use Modulation.
Check the Intellisys software revision level. Always update to the latest revision prior to operation.
Drawing Notes For Intellisys S3 Machines:
Note: R1 Relay - IR CCN: 39403290
Note: R1 Relay Base – IR CCN: 39125091
Guidance only; connections may differ with date, model, type, variant, special, custom or concession builds. This information is intended to
be used in conjunction with the compressor’s original control circuit diagram.
X4I Interconnect To Ingersoll Rand Intellisys S3 Page 74