Kohler 8/10/12RESV Welding System User Manual


 
TP-6880 10/14 57Section 4 DC2 Controller Operation
4.7 Maintenance Timer
The maintenance timer keeps track o f the time until the
next recommended maintenance a ccording to the
maintenance schedule for the generator set. Reset the
maintenancetimer afterchanging theoil andperforming
the other maintenance tasks recommended in
Section 5.
To reset the maintenance timer:
1. Press and hold the OFF and AUTO buttons
together until Maintenance Timer Reset is
displayed.
2. Release the OFF and AUTO buttons.
4.8 OnCue Plus Password
To set the OnCuerPluspassword onthe DC2controller,
1. Press the OFF button and verify that the generator
set is not running.
2. Press and hold the Exercise button until Press
Again to Reset OnCue PW is displayed.
3. Release the Exercise button and press it again
within 5 seconds.
Note: If the Exercise button is not pressed within 5
seconds, the controller exits the password
reset mode.
4. The gensetserial number and newpassword (PW)
will be displayed for 10 seconds. Record the
password for entry into the OnCuer Plus program.