17
ADV/FX/GEN---------------P00
ac2/gen 208 vac
lower limit
DOWN INC DEC PORT
ADV/FX/GEN---------------P00
ac2/gen 270 vac
upper limit
DOWN INC DEC PORT
ADV/FX/GEN---------------P00
ac2/gen 7.0 aac
input limit
DOWN INC DEC PORT
ADV/FX/GEN---------------P00
ac2/gen 60 cycles
transfer delay
DOWN INC DEC PORT
The ac/2 gen lower limit is the lowest allowable
voltage for the FX to connect to the generator.
If the voltage falls below this limit, the FX will
disconnect from the generator. This voltage value
is adjusted using and for values
between 80VAC and 220VAC. Press to
continue viewing the generator screens
The ac2/gen upper limit is the highest allow-
able voltage for the FX to remain connected to
the generator. If the voltage is higher than this
limit, the FX will disconnect from the generator.
This voltage value is adjusted using and
for values between 250VAC and 300VAC. Press
to view the ac2/gen input limit screen.
The ac2/gen input limit is the maximum current
the FX can draw from a generator. When this limit
is reached, the FX reduces its battery charging
function to prevent overloading the generator. If
the generator exceeds this limit, the FX will start
blinking the red ERROR LED as a warning. This
setting’s range is 1.0AAC to 30.0AAC, adjustable
using using and . Press
to continue.
The ac2/gen transfer delay is the amount of
time the FX remains connected to the genera-
tor after the AC input voltage drops below the
ac2/gen lower limit setting. This setting is adjusted
between 0 and 240 cycles using and
Press the soft key to view the next GEN
screen.