Outback Power Systems VFX3024E Battery Charger User Manual


 
33
The default value for the power save level slave
adjust only screen is 1. Press the <INC> or <DEC>
soft keys to adjust this value. Press the <PORT>
soft key to change the value of each Slave FX.
The Slave(s) must be connected to Port 2 or
higher on the HUB.
With the Master FX default value of zero in the
power save level master adjust only screen, all of
the Slave FX’s will remain OFF until the Master
FX needs help and calls for the Slave FXs with
“Slave Rank” equal to 1 to come ON.
• Choose a di erent “Slave Rank” for each Slave
FX. This helps assure proper operation and
allows them to come ON one at a time saving
power in the long run. Otherwise, with a
default value of 1 for all Slaves, they will all
come on whenever a 12 amp load calls for
more power, but then can quickly shut o
because multiple FXs provide far more than
the required 12 amps. Ranking them 1, 2, 3, 4
etc. means they will come on one at a time as
needed to better serve the loads and conserve
energy.
ADV/FX/STACK------------P02
power save level 1
slave adjust only
DOWN INC DEC PORT
ADV/FX/STACK-----------------
stacking setup
completed
TOP ADV MAIN
Press the <MAIN> soft key to return to the Main
Menu.
Press the <DOWN> soft key to view the  nal
stacking screen.