BATTERY CHARGING
Keeping your battery bank energized is very important. Although a battery bank can last for many
years if properly cared for, it can also be ruined in a short period of time if neglected.
Battery Charging Set Points
To preserve your batteries, always follow your battery manufacturer’s recommendations using the
following information:
• Absorb Voltage • Float Voltage • Equalize Voltage • Recommended Depth of Discharge (DOD)
Absorb, Float and Equalize voltage set points are programmed using the OutBack MATE.
MAINTENANCE
Please contact OutBack Power Systems Technical Services for any FX repairs due to malfunctions or damage.
For routine, user-approved maintenance:
• Disconnect all circuit breakers and related electrical connections before doing any cleaning or adjustments.
• Solar modules may produce hazardous voltages when exposed to light; cover them with opaque material
before servicing any connected equipment.
• If a remote or automatic generator start system is used, disable the automatic starting circuit and/or disconnect
the generator from its starting battery while servicing it to prevent starting while servicing.
ADV/FX/AUX---------------P00
diversion 14.6 vdc
on set point
DOWN INC DEC PORT
After deciding on Divert DC or Divert AC in the
AUX output function screen, use the diversion on
set point screen to choose the voltage which will
activate this function. This value can range from
12.0VDC-16.0VDC and can be adjusted in 0.1
VDC increments using the <INC> and <DEC>soft
keys. Press the <DOWN> soft key to view the
diversion o delay screen.
ADV/FX/AUX--------------P00
diversion 30 sec
o delay
DOWN INC DEC PORT
The diversion o relay determines how long the
AUX will be energized after the battery voltage
which caused the diversion falls below the diver
sion on set point. This relay can range from 0-240
seconds in one-second increments as adjusted
with the <INC> and <DEC> soft keys. Press the
<DOWN> soft key to view the nal aux output
setup completed screen.
ADV/FX/AUX----------------
aux output
setup completed