Outback Power Systems VFX3024E Battery Charger User Manual


 
44
ADV/FX/AUX-------------P00
aux output Remote
function
DOWN INC DEC PORT
From the Remote aux output function screen,
press the <DOWN> soft key. This will bring up
the  rst of several screen used to adjust which
ever mode you have chosen for the AUX
function.
ADV/FX/AUX---------------P00
genalert 11.5vdc
on set point
DOWN INC DEC PORT
The genalert on set point screen shows the
voltage--whose range is between 10.0VDC and
14.0VDC, adjusted with the <INC> and <DEC>
soft keys--at which the AUX is energized in
genalert mode. Press the <DOWN> soft key to
view the genelert on delay screen.
ADV/FX/AUX---------------P00
genalert 4 minutes
on delay
DOWN INC DEC PORT
The genalert on delay is the amount of time the
battery voltage must remain below the genalert
set point before the AUX is energized. This allows
for brief periods of heavy load usage and has a
range of 0-240 minutes in one minute increments,
adjustable with the <INC> and <DEC> soft keys.
Press the <DOWN> soft key to bring up the
genalert o set point screen.
ADV/FX/AUX---------------P00
genalert 14.0 vdc
o set point
DOWN INC DEC PORT
In genalert mode, the AUX de-energizes when
the genalert o set point is reached. This set
point’s range is between 12.0VDC and 18.0VDC
and is adjusted in 0.1 VDC increments using the
<INC> and <DEC> soft keys. Press the <DOWN>
soft key to view the genalert o delay screen.