Powerware 1085 Battery Charger User Manual


 
34
Po werware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
You should read and understand these general notes before beginning installation:
The material and labor for external wiring requirements is to be supplied by
others.
Power cables and control wiring must be installed in separate conduit.
The ground conductor is to be sized per NEC Article 250 and local electrical
code requirements.
The maximum current listed is at the minim um DC operating voltage.
Nominal voltages listed in this chapter are for a lead-acid battery plant rated per
NEC at 2.00 VDC per cell.
Battery cabinets must be installed in accordance with all applicable codes and
regulations, including the National Electrical Code (NEC), Article 480.
The UPS to battery cable should be sized for a total maximum voltage drop of
1% nominal DC link voltage at maximum current.
The external wiring specifications are outlined in Table C of Appendix A. Tables
A and B in this chapter detail the power cable terminations.
The remote battery disconnect weighs approximately 11.4 kg (25 lb) and has an
ampere interrupting capacity of 10,000 at 500 VDC.
Tightening Torque: 28.7 --- 31.1 N-M (255---275 lb-in.)
Internal Drive Hex Size: 5/16 in.
The knockout pattern for conduit is shown in Figure 21. If a larger size conduit
is required, the contractor may enlarge knockouts at your site during
installation.