Powerware 1085 Battery Charger User Manual


 
A --- 5
Po werware 9350 Series 685 and 1085 Auxiliary Battery Cabinets
Installation Manual 164201408 Rev. P00 053002
Table C. External Wiring Requirements (UPS-to-Battery or Remote Disconnect-to-Battery)
NOTE: All specified wire sizes are 90_C rated copper minimum UPS CabinetBattery Cabinet
UPS
Series/
Model
Torque
N-M
(lb-in)
Tool Size
Torque
N-M
(lb-in)
Tool Size
Wire
Size
UPS to
Battery
Integral
or
Separate
#of
Cabinets
Battery
Type*
Battery
Cabinet
Series
160/125 685 H20 2 Integral Supplied 3/8I hex
42.4
(375)
3/8I hex
42.4
(375)
160/125 685 H20 2 Separate
300
kcmil
3/8I hex
42.4
(375)
3/8I hex
42.4
(375)
160/125 1085
B27, B31,
B37, B47,
H30, H40,
H50
2, 3, or 4 Integral Supplied 3/8I hex
42.4
(375)
3/8I hex
42.4
(375)
160/125 1085
B27, B31,
B37, B47,
H30, H40,
H50
2, 3, or 4 Separate
300
kcmil
3/8I hex
42.4
(375)
3/8I hex
42.4
(375)
160/150 685 H20 2 Integral Supplied 3/8I hex
42.4
(375)
3/8I hex
42.4
(375)
160/150 685 H20 2 Separate
300
kcmil
3/8I hex
42.4
(375)
3/8I hex
42.4
(375)
160/150 1085
B27, B31,
B37, B47,
H30, H40,
H50
2, 3, or 4 Integral Supplied 3/8I hex
42.4
(375)
3/8I hex
42.4
(375)
160/150 1085
B27, B31,
B37, B47,
H30, H40,
H50
2, 3, or 4 Separate
300
kcmil
3/8I hex
42.4
(375)
3/8I hex
42.4
(375)
160/160 685 H20 2 Integral Supplied 3/8I hex
42.4
(375)
3/8I hex
42.4
(375)
160/160 685 H20 2 Separate
300
kcmil
3/8I hex
42.4
(375)
3/8I hex
42.4
(375)
160/160 1085
B27, B31,
B37, B47,
H30, H40,
H50
1, 2, 3,
or 4
Integral Supplied 3/8I hex
42.4
(375)
3/8I hex
42.4
(375)
160/160 1085
B27, B31,
B37, B47,
H30, H40,
H50
1, 2, 3,
or 4
Separate
350
kcmil
3/8I hex
42.4
(375)
3/8I hex
42.4
(375)
* BATTERY TYPE DESIGNATIONS: B = C&D, H = HAWKER
NOTE: The term “Se parate” refers to battery cabinets that are not physically attached to the
UPS, are wired with external contractor supplied wiring, and use a single overcurent
protection and disconnect device located near the batteries.
The term “Integral” refers to batte ry cabinets that are physically attached to the UPS
and the wiring between them is internal. The power wiring is supplied with the
system, and they use the UPS battery switch as the battery isolation device.
Thewiresizeratingforproductsuptoandincludingthe160/160areforthetotal
battery supply. Since these UPS units can only land one wire per DC connection
point, a common DC collector including an isolation device and overcurrent
protection should be used. Refer to applicable national or local code requirements
foryourinstallation.