Precision Trading 60 R3.0 Battery Charger User Manual


 
Operator Manual, Supercharger 60 R3.0
Page 17 of 62
3.5 DIGITAL PANEL METERS
3.5.1. VOLTMETER:
3.5.1.1. Accuracy (system): ±0.25% of reading, ±0.1V in the 200V scale,
±0.01V in the 20V scale, ±0.005V in the 2V scale.
3.5.1.2. Input impedance: 1 M-OHM.
3.5.1.3. Scale 2V, 20V and 200V (1.999V, 19.9V and 199.9V) for external
measurements and 20V and 200V for internal (battery) measurements.
3.5.2. AMMETER:
3.5.2.1. Accuracy (system): ±0.5% of reading, ±0.1A
3.5.2.2. Scale: 200A (199.9A)
3.5.3. SHUNT:
3.5.3.1. Accuracy: ±0.25%
3.5.3.2. Output: 1mV/A (100mV / 100A)
3.6 FUSES and BREAKERS (Other than charge and discharge current limiters)
3.6.1. Mains: Dual Magnetic Circuit Breaker
3.6.2. Electronics and digital panel meters: 1/4A SLO BLO.