Precision Trading 60 R3.0 Battery Charger User Manual


 
Operator Manual, Supercharger 60 R3.0
Page 24 of 62
5.2 CONSTANT VOLTAGE CHARGE.
5.2.1. The battery is charged at the topping rate for a preset time.
5.2.2. When the battery voltage is within 0.5V of the selected float voltage, the
charging current begins to diminish, and settles to the level of current required to
maintain the battery at the selected float voltage.
5.2.3. Charging is automatically terminated at the end of the total time selected (cycle
end), or as a fault if:
Battery overtemperature is detected (Overtemp fault).
Battery voltage is in excess of 85V (voltage fault).
Actual charging current differs from the programmed value by more than 1
AMP (current fault).
Note: applicable only before the charger switches from
constant current to constant voltage.
5.2.4. Charge operation may be terminated at any time by depressing the (green) reset
button.