Note: See Chapter 7, “Parts listing, BladeCenter Type 8677 and 1881,” on page 79 to determine which components
should be replaced by a field service technician.
Message Action
System is under recommended voltage
for +5V
1. Reseat the management module.
2. Replace the management module.
System running nonredundant power Ensure that power modules 1 and 2 are installed and operating
correctly. If blade servers are installed in bay 7 or higher, ensure
that power modules 3 and 4 are installed and working correctly.
Blade server error messages
Note: See Chapter 7, “Parts listing, BladeCenter Type 8677 and 1881,” on page 79 to determine which components
should be replaced by a field service technician.
Message Action
Blade server x was installed Information only. Take action as required.
Blade server x was removed Information only. Take action as required.
Received an [xxx] alert from an
unsupported ISMP type xxxx, via the
interconnect network
Ensure that all blade servers in the blade center are supported by
the management module.
KVM error message
Note: See Chapter 7, “Parts listing, BladeCenter Type 8677 and 1881,” on page 79 to determine which components
should be replaced by a field service technician.
Message Action
Error encountered switching KVM owner,
see system error log
1. Reseat the blade server.
2. Reseat the management module.
3. Reflash the blade server H8 firmware.
4. Replace the blade server.
5. Replace the management module.
6. Replace the midplane.
I/O module error messages
Note: See Chapter 7, “Parts listing, BladeCenter Type 8677 and 1881,” on page 79 to determine which components
should be replaced by a field service technician.
Message Action
Switch fault x
1. Reseat I/O module x.
2. Replace I/O module x.
Switch module x was removed Information only. Take action as required.
Switch module x was installed Information only. Take action as required.
Switch module x was powered on Information only. Take action as required.
Switch module x was powered on Information only. Take action as required.
Switch System running nonredundant
switch modules
Information only. Take action as required.
74 BladeCenter E Type 8677 and 1881: Hardware Maintenance Manual and Troubleshooting Guide