Floor Loading
When planning the installation, consider the UPS weight for floor
loading. The strength of the installation surface must be adequate for
point and distributed loadings. The approximate weights are shown in
the following table.
Standard Model Floor Loadings (2-High/3-High Cabinets)
Powerware 9155
Maximum
Weight (lb)
Point Loading
(lb/in
2
)
Distributed
Loading (lb/ft
2
)
2-High UPS 352 88 166
3-High UPS 590 148 278
3-High UPS with
Isolation
Transformer
558 140 263
2-High EBM 480 120 226
3-High EBM 710 178 335
Clearances
The following clearances are recommended for the Powerware 9155
UPS:
From Front of Cabinet 36(91.4 cm) working space
From Back of Cabinet 6(15.2 cm)