9155 Parallel UPS (8–15 kVA) User’s Guide S 164201592 Rev C www.powerware.com
43
Table 4. User Settings (continued)
Default SettingAvailable SettingsDescription
Modem Config
Modem Installation <Not Installed>
Set Modem Call Events Event #0
Call modem: no
Set Modem Init String ATZ0
Set Modem Call Command None
Set Modem Communication Password None
Start Screen Eaton Powerware logo
Mimic screen
Eaton Powerware logo
User Password Enabled/Disabled
If Enabled is selected, the password is USER.
Disabled
Audible Alarms Normal Sound/Disabled Normal Sound
Battery Charging ABM cycling/constant ABM cycling
Automatic Battery Tests Enabled/Disabled
Enabled automatically runs the battery test
once a month.
Enabled
Full Power Battery Test Enabled/Disabled Enabled
Number of Battery Strings 0 through 22
(see “Configuring the UPS for EBMs” on
page 49)
2 strings for UPS-32 models
4 strings for UPS-64 models
Battery Capacity 1 through 65535 watts per cell 34 W/cell
Battery Low Alarm Level 1.750 through 1.950 volts per cell 1.880 V/cell
Set Nominal Output Voltage 120V/240V
120V/208V
110V/220V
100V/200V
127V/220V
120V/208V
Bypass Voltage High Limit +1 through +20% (1% increments) 120V +10%
Bypass Voltage Low Limit -1 through -20% (1% increments) 120V -15%
Nominal Output Frequency 50 Hz or 60 Hz 60 Hz
Synchronization Enabled/Disabled Enabled