User Settings
The following table displays the options that can be changed by the
user.
NOTE Changes to the output voltage or frequency options should be made before turning
on the UPS; otherwise, the changes do not take effect.
Table 4. User Settings
Description Available Settings Default Setting
Set Date and Time Set Month
Date: mm/dd/yyyy
Time: 24:00
01/01/2003
00:00
Display Contrast Adjust contrast with up/down arrow buttons Moderate
Change Language Select Language: <English>
Elegir idioma <Español>
English
Relay Config Relay: [Alarm 1] [X-Slot 1-1/2/3/4] or
[X-Slot 2-1/2/3/4]
Setup: [empty] [On Battery] [summary alarm]
[On Bypass] [UPS ok] [custom]
Alarm1:empty
X-Slots(1or2)
#1: UPS ok
#2: On Bypass
#3: Summary Alarm
#4: On Battery
Signal Inputs [empty] [Logic]
Signal Input must be wired to the CAN Bridge
Card (see Figure 19 on page 27).
For more information, refer to “Programmable
Signal Inputs” in the Powerware 9155 UPS
(8–15 kVA) User’s Guide.
<empty>
Serial Port Config Port: [X-Slot-1] [X-Slot-2/Serv]
Speed: [19200] [9600] [2400] [1200]
19200
Parallel Operation Settings
Parallel Unit N umber: [Single Unit] [Unit #1]
[Unit #2] [Unit #3]
Single Unit
Start Auto Calibration: [Press ]
Redundant Mode
Capacity Mode
Redundant Mode