PRELIMINARY HARDWARE SETTINGS
1) Remove the instrument from its case.
2) Set J106 according to the following table:
E) Power Line and grounding
R (S,T), L1
NOTE:
1) Before connecting the power line, check that the
voltage is correct (see Model Number).
2) For supply connections use 16 AWG or larger wires
rated for at least 75 °C.
3) Use copper conductors only.
4) Do not run input wires with power cables.
5) Polarity does not matter for 24 Vdc wiring.
6) The power supply input is
not
fuse protected.
Please provide it externally.
ylppuSrewoPepyTtnerruCegatloV
cdV/caV42TAm005V052
caV042/001TAm521V052
When the fuse is damaged the instrument should be
returned to your supplier to check the power supply.
7) Safety requirements for permanently connected
equipment:
- Include a switch or circuit-breaker in the
installation.
- Place the switch in close proximity to the
equipment and within easy reach of the
operator.
- Mark the switch as the disconnecting device for
the equipment. NOTE: A single switch or
circuit-breaker can drive more than one
instrument.
8) When the NEUTRAL line is present, connect it to
terminal 4.
9) To avoid shock and possible instrument damage,
connect power last.
epyTtupnI
601J
2-14-36-58-7
,DTR,C/T
Vm06-21,Vm06-0
)noitarugifnocdradnats(
esolc
nepo
nepo nepo
V5-1,V5-0
nepo esolc nepo nepo
V01-2,V01-0
nepo nepo esolc nepo
Am02-4,Am02-0
nepo nepo nepo esolc
K081=291RCTTCtupnI
nepO=101HCdesolC=021HS
4
5
POWER SUPPLY
100 to 240 Vac
24 Vac/Vdc
N, L2
R (S,T), L1
N, L2
7sl-1-00.p65 9/17/02, 2:39 PM12