r1 = Input Type and Range Value
0 = TC J From -100 to 1000 °C
1 = TC K From -100 to 1370 °C
2 = TC T From -200 to 400 °C
3 = TC E From -100 to 800 °C
4 = TC N From -100 to 1400 °C
5 = TC S From -50 to 1760 °C
6 = TC R From -50 to 1760 °C
7 = TC B From 0 to 1820 °C
8 = TC L From -100 to 900 °C
9 = TC U From -200 to 600 °C
10= TC G From 0 to 2300 °C
11= TC D From 0 to 2300 °C
12= TC C From 0 to 2300 °C
13= TC Plat. II From -100 to 1400 °C
14= RTD Pt 100 From -200 to 850 °C
15= Linear From 0 to 60 mV
16= Linear From 12 to 60 mV
17= Linear From 0 to 20 mA
18= Linear From 4 to 20 mA
19= Linear From 0 to 5 V
20= Linear From 1 to 5 V
21= Linear From 0 to 10 V
22= Linear From 2 to 10 V
23= TC J From -150 to 1830 °F
24= TC K From -150 to 2500 °F
25= TC T From -330 to 750 °F
26= TC E From -150 to 1470 °F
27= TC N From -150 to 2550 °F
28= TC S From -60 to 3200 °F
29= TC R From -60 to 3200 °F
30= TC B From 32 to 3300 °F
31= TC L From -150 to 1650 °F
32= TC U From -330 to 1110 °F
33= TC G From 0 to 4170 °F
34= TC D From 0 to 4170 °F
35= TC C From 0 to 4170 °F
36= TC Plat. II From -150 to 2550 °F
37= RTD Pt100 From -330 to 1560 °F
r2 = Decimal Point Position
(Available only for linear range r1 = 15 to 22)
_ _ _ _ . = No decimal
_ _ _ . _ = One decimal place
_ _ . _ _ = Two decimal places
_ . _ _ _ = Three decimal places
r3 = Low Scale Range Value
(Available only for linear range r1 = 15 to 22)
Range: From -1999 to 9999
r4 = High Scale Range Value
(Available only for linear range r1 = 15 to 22)
Range: From -1999 to 9999
r5 = Offset Adjustment
Range: From -500 to 500
Offset value algebraically added to the measured value.
r6 = Time Constant for Filter on Displayed Value
Range: From 0 (filter OFF) to 8 seconds.
(First order filter with selected time constant.)
r7 = Alarm Action on Fault
uP = The alarm assumes an upscale reading.
doun = The alarm assumes a downscale reading.
C1 = Type of Limit Action
Hi. = High limit (for heating process)
Lo. = Low limit (for cooling process)
Hi.Lo = Band limit (for special process)
C2 = Acknowledgment Mode
O = The acknowledgment action is ignored if performed
when setpoint is exceeded.
I = The acknowledgment action is recognized also
when the setpoint is exceeded. (In this case, the
control output is instantaneously restored when
process variable is within setpoint).