NOTE:
1) Do not run input wires with power cables.
2) High line resistance can cause measurement
errors.
3) When shielded cable is used, ground it at one end
only to avoid ground loop currents.
4) The input impedance is equal to:
Less than 5 for 20 mAdc input
Greater than 1 M for 60 mVdc input
Greater than 400 K for 5 Vdc and 10 Vdc input
10
9
Shield
_
+
mA,
mV
or
V
_
+
10
9
+
_
G
mA
mV
or
V
_
+
Linear Input
14
15
Logic input
B) Logic Input
This input is used as a remote reset.
Safety note:
- Do not run logic input wiring with AC power cables.
- Use an external contact with a contact rating
greater than 0.5 mA, 5 Vdc.
- The instrument needs 100 ms to recognize a
contact status variation.
NOTE:
1) Do not run RTD wires with power cables.
2) Ground shielded cable at one end only.
3) Use the correct size copper wires.
4) The resistance of the 3 wires must be the same.
RTD
109
8
109
8
RTD
RTD Input