DEFAULT PARAMETERS
Loading Default Operating Parameters
The control parameters can be loaded with predeter-
mined default values. These are the settings loaded into
the instrument prior to shipment from the factory. To load
the default values proceed as follows:
a) Press and hold the key and press the key; the
displays will show:
b) Press either the or key; the display will show:
c) Press the "FUNC" key; the display will show:
This indicates that the loading procedure has been
initiated. After about 3 seconds the loading procedure is
complete and the instrument reverts to the “Normal
Display Mode.” The following is a list of the default
operating parameters loaded during the procedure:
Default Operating Parameters List
Parameter Default Value
Alarm Acknowledge OFF
Software Key Unlock
Setpoint Threshold Low range value (if low limit)
High range value (if high or high/
low limit)
Setpoint1 Threshold Low range value
Setpoint Threshold
Hysteresis 0.1%
Alarm Threshold Low range (if process alarm)
100 (if deviation or band alarm)
Alarm Hysteresis 0.1%
Loading Default Configuration Parameters
The configuration parameters can be loaded with prede-
termined default values. These are the settings loaded
into the instrument prior to shipment from the factory. To
load the default values proceed as follows:
a) Internal switch V101 must be open.
b) The upper display will show:
c) Press the key; the lower display will show the
firmware version.