CONFIGURATION KEY FUNCTIONS
RESET In Configuration Mode, used only to scroll
back parameters
Used in Configuration Mode to decrease the
parameter value.
Used in Configuration Mode to increase the
parameter value.
FUNC Monitors/Modifies parameters.
+ Loads the default parameters.
+ FUNC or + FUNC
Increases/decreases values at a higher rate
when modifying parameters.
+ RESET or + RESET
Jumps to the Maximum or Minimum parameter
value when modifying parameters.
CONFIGURATION PROCEDURE
1) Remove the instrument from its case.
2) Open switch V101 (See illustrations under “Prelimi-
nary Hardware Settings.”)
3) Re-insert the instrument in its case.
4) Switch on power to the instrument.
The upper display will show COnF.
5) Press the “ ” key and the lower display will show the
firmware version.
Press the "FUNC" key to start the configuration proce-
dure with the first parameter (L1). Press the "RESET"
key to start the configuration procedure with the last
parameter (d1).
The following is a complete list of parameters. The lower
display will show the parameter code (L1 to d1) and the
upper display will show the selection code or numerical
value. No timeout is applied in the configuration mode.
L1 = Serial Interface Protocol
(Skipped if option is not available.)
OFF = No serial interface
nbUS= Modbus
jbUS = Jbus
L2 = Serial Link Device Address
(Skipped if option is not available or L1 = OFF)
From 1 to 255
NOTE: The device can connect up to 31 instruments.
L3 = Baud Rate for Serial Link
(Skipped if option is not available or L1 = OFF)
Set value from 600 to 19200 baud.
(19200 baud is shown on display as 1920)
L4 = Byte Format for Serial Link
(Skipped if option is not available or L1 = OFF)
8E = 8 bits + even parity
8O = 8 bits + odd parity
8 = 8 bits without parity
7sl-2-00.p65 9/17/02, 2:40 PM14