York YR Air Compressor User Manual


 
18
YORK INTERNATIONAL
FORM 160.81-EG1
MARINE WATER BOXES
Marine water boxes allow service access for cleaning
of the heat exchanger tubes without the need to break
the water piping. Bolted-on covers are arranged for con-
venient access. Victaulic nozzle connections are stan-
dard; flanges are optional. Marine water boxes are avail-
able for condenser and/or evaporator.
KNOCK-DOWN SHIPMENT
The chiller can be shipped knocked-down into major
assemblies (evaporator, condenser, driveline, etc.) as
required to rig into tight spaces. This is particularly con-
venient for existing buildings where equipment room
access does not allow rigging a factory packaged chiller.
REFRIGERANT STORAGE/RECYCLING SYSTEM
A refrigerant storage/recycling system is a self-contained
package consisting of a refrigerant compressor with oil
separator, storage receiver, water-cooled condenser, fil-
ter drier and necessary valves and hoses to remove,
replace and distill refrigerant. All necessary controls and
safety devices are a permanent part of the system. Typi-
cally not required if unit isolation valves are provided.
Accessories and Modifications (continued)
SI Metric Conversion
The following factors can be used to convert from English to the most common Sl Metric values.
MEASUREMENT
MULTIPLY THIS
BY
TO OBTAIN THIS
ENGLISH VALUE METRIC VALUE
CAPACITY TONS REFRIGERANT EFFECT (ton) 3.516 KILOWATTS (kW)
POWER
KILOWATTS (kW) NO CHANGE KILOWATTS (kW)
HORSEPOWER (hp) 0.7457 KILOWATTS (kW)
FLOW RATE GALLONS / MINUTE (gpm) 0.0631 LITERS / SECOND (L/s)
LENGTH
FEET (ft) 304.8 MILLIMETERS (mm)
INCHES (in) 25.4 MILLIMETERS (mm)
WEIGHT POUNDS (lb) 0.4536 KILOGRAMS (kg)
VELOCITY FEET / SECOND (fps) 0.3048 METERS / SECOND (m/s)
PRESSURE DROP
FEET OF WATER (ft) 2.989 KILOPASCALS (k Pa)
POUNDS / SQ. INCH (psi) 6.895 KILOPASCALS (k Pa)
Integrated Part Load Value (IPLV)
In the English I-P system, IPLV is calculated by the fol-
lowing formula. A full explanation is shown on page 4:
1
IPLV*=
0.01
+
0.42
+
0.45
+
0.12
ABCD
Where: A = kW / ton at 100% Load @ 85°F ECFT
B = kW / ton at 75% Load @ 75°F ECFT
C = kW / ton at 50% Load @ 65°F ECFT
D = kW / ton at 25% Load @ 65°F ECFT
In SI Metric, the formula is:
IPLV* = 0.01A + 0.42B + 0.45C + 0.12D
Where: A = COP at 100% Load @ 29.4°C ECFT
B = COP at 75% Load @ 23.9°C ECFT
C = COP at 50% Load @ 18.3°C ECFT
D = COP at 25% Load @ 18.3°C ECFT
NOTE:
* The Non-Standard Part-Load Value (NPLV) uses the IPLV formula
with the following exceptions: the ECFT for part-load points varies
linearly from the selected EFT to 65°F (18.3°C) from 100% to 50%
loads, and fixed at 65°F (18.3°C) for 50% to 0% loads.