York YR Air Compressor User Manual


 
31
YORK INTERNATIONAL
FORM 160.81-EG1
Dimensions (mm) – Nozzle Arrangements
CONDENSERS – COMPACT WATER BOXES
NOTES:
1. Standard water nozzles are furnished as welding stub-outs with Victaulic grooves, allowing the option of welding, flanges, or use of
Victaulic couplings. Factory installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1.59 mm raised face), water
flanged nozzles are optional (add 12.7 mm to nozzle length). Companion flanges, nuts, bolts, and gaskets are not furnished.
2. Add 25.4 mm for isolators as shown.
3. One-, two- and three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of condenser nozzles
may be used in combination with any pair of evaporator nozzles.
4. Connected piping should allow for removal of compact water boxes for tube access and cleaning.
5. Front of unit is defined as side of chiller where control center is mounted.
NOZZLE
ARRANGEMENTS
NO. OF COND.
PASSES IN OUT
1
PQ
QP
NOZZLE
ARRANGEMENTS
NO. OF COND.
PASSES IN OUT
2
RS
TU
NOTE: Water must enter
through bottom connection to
achieve rated performance
NOZZLE
ARRANGEMENTS
NO. OF COND.
PASSES IN OUT
3
VY
XW
NOTE: Water must enter
through bottom connection to
achieve rated performance
LD07983
CONDENSER
CONDENSER NOZZLE PIPE SIZE
NOZZLE DIMENSIONS
SHELL
NO. OF PASSES 1-PASS 2-PASS 3-PASS
CODE
12 3CC
2
GG BB
2
DD
2
GG BB
2
DD
2
GG
T, V 10" 6" 6" 730 381 553 908 381 553 908 381
W, X 12" 8" 6" 781 394 584 978 394 584 978 394
1-PASS
2-PASS
3-PASS
MOTOR END
MOTOR END
MOTOR END
COMPRESSOR END
COMPRESSOR END
COMPRESSOR END
FLOOR LINE
FLOOR LINE
FLOOR LINE
1"
1"
1"
1"
1" 1"
GG GG
GG GG
GG
GG
CC CC
DD
BB
DD
BB
DD
BB
DD
BB
QP
U
S
T
R
Y
W
X
V
FRONT
OF UNIT
FRONT
OF UNIT
FRONT
OF UNIT
FRONT
OF UNIT
FRONT
OF UNIT
FRONT
OF UNIT
CONDENSER CONDENSER
CONDENSER CONDENSER
CONDENSER CONDENSER