Programmable:
Full-load Amps
Voltage Range
Starting Current
Open SCR
Shorted SCR
kWH Reset
The SETPOINTS screen provides a convenient loca-
tion for programming the most common setpoints in-
volved in the chiller control. The Setpoints are shown
on other individual screens, but to cut down on need-
less searching, they can all be found on this screen.
This screen also serves as a gateway to a sub-screen
for defining the setup of general system parameters.
From this screen you can perform the following:
Display Only:
Leaving Chilled Liquid Temperature – Setpoint
Leaving Chilled Liquid Temperature Cycling –
Shutdown
Leaving Chilled Liquid Temperature Cycling –
Restart
Current Limit Setpoint
Programmable:
Local Leaving Chilled Liquid Temperature – Range
Local Leaving Chilled Liquid Temperature – Setpoint
Leaving Chilled Liquid Temperature Cycling Offset –
Shutdown
Leaving Chilled Liquid Temperature Cycling Offset –
Restart
Remote Analog Input Range
Local Motor Current Limit
Pulldown Demand Limit
Pulldown Demand Time
Print
The SETUP is the top level of the general configura-
tion parameters. It allows programming of the time and
date, along with specifications as to how the time will
be displayed. In addition, the chiller configuration as
determined by the Micro Board program jumpers and
program switches is displayed. From this screen you
can perform the following:
Display Only:
Chilled Liquid Pump Operation (Displays Standard
or Enhanced)
Anti-Recycle (Displays Disabled or Enabled)
Power Failure Restart (Displays Manual or Automatic)
Liquid Type (Displays Water or Brine)
Programmable:
Set Date
Set Time
Clock (Enabled/Disabled)
12/24 Hour
The following six subscreens can be accessed from
the SETUP screen:
The SCHEDULE screen contains more programmable
values than a normal display screen. Each program-
mable value is not linked to a specific button; instead,
the select key is used to enable the cursor arrows and
check key to program the Start/Stop times for any day
of the week up to 6 weeks in advance. The user has
the ability to define a standard set of Start/Stop times
that are utilized every week or specify exceptions to
create a special week.
Programmable:
Exception Start/Stop Times
Schedule (Enable/Disable)
Repeat Sunday Schedule
Standard Week Start/Stop Times
Reset All Exception Days
Select
Print