The EVAPORATOR screen displays a cutaway view of
the chiller evaporator. All setpoints relating to the evapo-
rator side of the chiller are maintained on this screen.
Animation of the evaporation process indicates whether
the chiller is presently in RUN condition (bubbling) and
liquid flow in the pipes is indicated by alternating shades
of color moving in and out of the pipes. Adjustable lim-
its on the low water temperature setpoints allow the
chiller to cycle on and off for greater efficiency and less
chiller cycling. The chiller cycles off when the leaving
chilled water temperature is below setpoint and is ad-
justable from 1°F (0.55°C) below to a minimum of 36°F
(2.22°C). Restart is adjustable from setpoint up to a
max. of 80°F (26.6°C). The Panel will check for flow to
avoid freeze-up of the tubes. If flow is interrupted, shut-
down will occur after a minimum of two seconds. The
following can also be performed through this screen:
Display Only:
Chilled Liquid Flow Switch (Open/Closed)
Chilled Liquid Pump (Run/Stop)
Evaporator Pressure
Evaporator Saturation Temperature
Return Chilled Liquid Temperature
Leaving Chilled Liquid Temperature
Evaporator Refrigerant Temperature
Small Temperature Difference
Leaving Chilled Liquid Temperature Setpoints –
Setpoint
Leaving Chilled Liquid Temperature Setpoints –
Remote Range
Leaving Chilled Liquid Temperature Setpoints –
Shutdown
Leaving Chilled Liquid Temperature Setpoints –
Shutdown Offset
Leaving Chilled Liquid Temperature Setpoints –
Restart
Leaving Chilled Liquid Temperature Setpoints –
Restart Offset
Ice Storage Active (LED)
Programmable:
Local Leaving Chilled Liquid Temperature – Range
Local Leaving Chilled Liquid Temperature – Setpoint
Leaving Chilled Liquid Temperature Cycling Offset –
Shutdown
Leaving Chilled Liquid Temperature Cycling Offset –
Restart
The CONDENSER screen displays a cutaway view of
the chiller condenser. The liquid flow is animated to in-
dicate flow through the condenser. All setpoints relat-
ing to the condenser side of the chiller are maintained
on this screen. With the proper access level this screen
also serves as a gateway to controlling the Refrigerant
Level. The following can also be viewed through this
screen:
Display Only:
Leaving Condenser Liquid Temperature
Return Condenser Liquid Temperature
Condenser Pressure
Condenser Saturation Temperature
Small Temperature Difference
High Pressure Switch (Open/Closed)
Condenser Liquid Flow Switch
Condenser Liquid Pump (Run/Stop)
Programmable:
High Pressure Warning Threshold
Freeze Warning (Enabled/Disabled)
Freeze Time
The COMPRESSOR screen displays a cutaway view
of the chiller compressor, revealing the rotary screw,
and shows all conditions associated with the compres-
sor. The slide valve positioning is animated and with
the proper Access level, it can be manually controlled.
Animation of the compressor rotors indicates whether
the chiller is presently in a RUN condition. This screen
also serves as a gateway to sub-screens for calibrating
the slide valve or configuring the optional Hot Gas By-
pass. From this screen you can view the following:
Display Only:
Differential Oil Pressure
Oil Temperature
Discharge Temperature
Discharge Superheat
Slide Valve Position
Oil Return Solenoid (LED)
Full-load Amps (E.M. Starter Only)
Phase A, B, C Current (SSS Only)
Programmable:
Slide Valve Load (Manual)
Slide Valve Hold (Manual)