Selection of operation mode and operation location
4
PARAMETERS
4.15 Selection of operation mode and operation location
4.15.1 Operation mode selection (Pr. 79)
The above parameter can be changed during a stop in any operation mode.
Purpose Parameter that should be Set Refer to Page
Operation mode selection Operation mode selection Pr. 79
147
Started in Network operation mode Operation mode at power-on Pr. 79, Pr. 340
159
Selection of operation location
Operation command source and speed
command source during communication
operation, selection of operation location
Pr. 338, Pr. 339
Pr. 551
160
Used to select the operation mode of the drive unit.
Mode can be changed as desired among operation using external command signals (External operation), operation
from the operation panel and PU (FR-PU07) (PU operation), combined operation of PU operation and External
operation (External/PU combined operation), and Network operation (when RS-485 communication is used).
Parameter
Number
Name Initial Value Setting Range
79 Operation mode selection 0 0 to 4, 6, 7
POINT
Use the easy setting mode to set Pr. 79 in simple steps. (Refer to page 50)
Pr.79
Setting
Description
LED Indication
: OFF : ON
Refer
to
Page
0
(Initial
value)
Use External/PU switchover mode (At power ON, the drive unit is in the External operation
mode.)
Press to switch between the PU and External operation mode.
PU operation mode
External operation mode
NET operation mode
150
1
Operation mode Speed command Start command
PU operation mode
150
PU operation mode (fixed)
Setting by the operation
panel and PU (FR-PU07)
Input by on the
operation panel or and
on PU (FR-PU07)
2
External operation mode (fixed)
The operation can be performed
by switching between the
External and NET operation
modes.
External signal input (from
terminal 2, 4, JOG, multi-
speed selection, etc.)
External signal input (from
terminal STF and STR)
External operation mode
NET operation mode
150
3
External/PU combined
operation mode 1
Operation panel and PU (FR-
PU07) setting or external
signal input (multi-speed
setting, across terminals 4
and 5 (valid when AU signal
turns ON)).
External signal input (from
terminal STF and STR)
External/PU combined
operation mode
151
4
External/PU combined
operation mode 2
External signal input
(Terminal 2, 4, JOG, multi-
speed selection, etc.)
Input by on the
operation panel or and
on PU (FR-PU07)
151
6
Switchover mode
Switch among PU operation, External operating, and NET operation while keeping the
same operating status.
PU operation mode
External operation mode
NET operation mode
152
7
External operation mode (PU operation interlock)
X12 signal ON: Operation mode can be switched to the PU operation mode.
(output stop during External operation)
X12 signal OFF: Operation mode cannot be switched to the PU operation mode.
152
The priorities of the speed commands when Pr. 79 = "3" are "Multi-speed operation (RL/RM/RH/REX) > PID control (X14) > terminal 4 analog input (AU) >
digital input from the operation panel".
REMARKS
If switching of the operation mode is invalid even though Pr. 79 is set, refer to page 253.