Selection of operation mode and operation location
4
PARAMETERS
4.15.5 Operation mode at power-ON (Pr. 79, Pr. 340)
(1) Specify operation mode at power-ON (Pr. 340)
Depending on the Pr. 79 and Pr. 340 settings, the operation mode at power-ON (reset) changes as described below.
When power is switched ON or when power comes back ON after instantaneous power failure, the drive unit can be
started up in the Network operation mode.
After the drive unit has started up in the Network operation mode, parameter write and operation can be performed
from a program.
Set this mode for communication operation using PU connector.
Parameter
Number
Name Initial Value Setting Range Description
79 Operation mode selection
0 0 to 4, 6, 7
Operation mode selection
(Refer to page 149)
340 ∗
Communication startup
mode selection
0
0 As set in Pr. 79.
1 Network operation mode
10
Network operation mode
Operation mode can be changed between
the PU operation mode and Network
operation mode from the operation panel.
The above parameters can be changed during a stop in any operation mode.
* This parameter can be set when
Pr. 160 Extended function display selection = "0". (Refer to page 144)
Pr. 340
Setting
Pr. 79
Setting
Operation Mode at Power-ON, Power
Restoration, Reset
Operation Mode Switching
0
(initial
value)
0
(initial
value)
External operation mode
Switching among the External, PU and NET operation mode is
enabled ∗1
1 PU operation mode Fixed to PU operation mode
2 External operation mode
Switching between the External and NET operation mode is
enabled
Switching to PU operation mode disabled
3, 4 External/PU combined mode Operation mode switching disabled
6 External operation mode
Switching among the External, PU, and NET operation mode
is enabled while running.
7
External operation mode when X12 (MRS) signal
ON
Switching among the External, PU and Net operation mode is
enabled ∗1
External operation mode when X12 (MRS) signal
OFF
Fixed to External operation mode (Forcibly switched to
External operation mode.)
1
0
NET operation mode
Same as when Pr. 340 = "0"
1 PU operation mode
2
NET operation mode
3, 4 External/PU combined mode
6
NET operation mode
7
NET operation mode when X12 (MRS) signal ON
External operation mode when X12(MRS) signal
OFF
10
0
NET operation mode
Switching between the PU and NET operation mode is
enabled ∗2
1 PU operation mode Same as when Pr. 340 = "0"
2
NET operation mode Fixed to NET operation mode
3, 4 External/PU combined mode Same as when Pr. 340 = "0"
6
NET operation mode
Switching between the PU and NET operation mode is
enabled while running ∗2
7 External operation mode Same as when Pr. 340 = "0"
∗1 Operation mode can not be directly changed between the PU operation mode and Network operation mode
∗2 Operation mode can be changed between the PU operation mode and Network operation mode with key of the operation panel and X65 signal.
Parameters referred to
Pr. 79 Operation mode selection Refer to page 147