208
Special operation and speed control
<Set point input calibration>
1)Setting with terminal 2 input
1.Apply the input voltage of 0% set point setting (e.g. 0V) across terminals 2 and 5.
2.Enter in C2 (Pr. 902) the speed which should be output by the drive unit at the deviation of 0% (e.g. 0r/min).
3.In C3 (Pr. 902), set the voltage value at 0%.
4.Apply the voltage of 100% set point (e.g. 5V) across terminals 2 and 5.
5.Enter in Pr. 125 the speed which should be output by the drive unit at the deviation of 100% (e.g. 3000r/min).
6.In C4 (Pr. 903), set the voltage value at 100%.
2) Setting with Pr. 133
(When both or one of C42 (Pr. 934) and C44 (Pr. 935) is "9999".)
For the set point, set a % converted value in the range of 0 to 100%.
(When both of C42 (Pr. 934) and C44 (Pr. 935) ≠ "9999".)
For the set point, set PID coefficient, which corresponds with 0 to 100%.
<Measured value calibration>
1)When both or one of C42 (Pr. 934) and C44 (Pr. 935) is "9999"
1.Apply the input current of 0% measured value (e.g. 4mA) across terminals 4 and 5.
2.Make calibration using C6 (Pr. 904).
3.Apply the input current of 100% measured value (e.g. 20mA) across terminals 4 and 5.
4.Make calibration using C7 (Pr. 905).
2) When both of C42 (Pr. 934) and C44 (Pr. 935) ≠ "9999"
1.Apply the input current of 0% measured value (e.g. 4mA) across terminals 4 and 5.
2.Set PID display value at 0% measured value (example: 15(°C)) to C42 (Pr. 934) , and calibrate C43 (Pr. 934).
3.Apply the input current of 100% measured value (e.g. 20mA) across terminals 4 and 5.
4.Set PID display value at 100% measured value (example: 35(°C)) to C44 (Pr. 935), and calibrate C45 (Pr. 935).
The results of the above calibration are as shown below:
REMARKS
The speed set in C5 (Pr. 904) and Pr. 126 should be the same as set in C2 (Pr. 902) and Pr. 125 .
Pr. 133
Setting
Pr. 934,
Pr. 935
Setting
Set Point Setting
Measured Value
(Terminal 4)
Manipulated Variable
9999 —
(Terminal 2)
Other than
9999
Both or one
is 9999
(Pr. 133)
Set a % converted value in the
range of 0 to 100%.
Other than
9999
(Pr. 133)
Set PID coefficient
corresponding with 0 to 100%.
100
0
0
5(V)
Set point signal input
Set point
(%)
100
0
0
20
C7(Pr. 905)
(mA)
Measured value
input signal
Measured
Value
(%)
4
C6(Pr. 904)
3000
(Pr. 125)
0
C2(Pr. 902)
0
100
Deviation(%)
Manipulated
Variable(r/min)
100
0
C5(Pr. 904)
Pr. 126
Set point setting
Set point
(%)
100
0
C42(Pr. 934)
C44(Pr. 935)
Set point
(%)
100
0
0
20
C45(Pr. 935)
(mA)
Measured value
input signal
Measured
value
(%)
4
C43(Pr. 934)