200
Special operation and speed control
577
Output interruption
cancel level
1000%
∗4
900 to 1100%
∗4
Set the level (Pr. 577 minus 1000%) at which the PID output
interruption function is canceled.
C42
(934)
∗5
PID display bias
coefficient
9999
0 to 500.00 Set the coefficient on bias (minimum) side of terminal 4 input.
9999 Displayed in %.
C43
(934)
∗5
PID display bias
analog value
20% 0 to 300.0%
Set the converted % on bias (minimum) side current /voltage of
terminal 4 input.
C44
(935)
∗5
PID display gain
coefficient
9999
0 to 500.00 Set the coefficient on gain (maximum) side of the terminal 4 input.
9999 Displayed in %.
C45
(935)
∗5
PID display gain
analog value
100% 0 to 300.0%
Set the converted % on gain (maximum) side of current/voltage of
terminal 4 input.
The above parameters can be set when Pr. 160 Extended function display selection = "0". (Refer to page 144)
∗1 Pr. 129, Pr. 130, Pr. 133 and Pr. 134 can be set during operation. These can also be set independently of the operation mode.
∗2 Differs according to capacities. (0.2K to 2.2K/3.7K)
∗3 If a value exceeding 3000r/min is set, the actual rotation speed will be limited at 3000r/min.
∗4 If C42 (Pr. 934) and C44 (Pr. 935) are both set to values other than "9999", the setting range for Pr. 131 to Pr. 133 and Pr. 553 become only "9999", and % is
not displayed in the setting range of Pr. 577. (Values set in Pr. 553 and Pr. 577 are converted as differentials.)
∗5 The parameter number in parentheses is the one for use with the parameter unit (FR-PU07).
Parameter
Number
Name
Initial
Value
Setting
Range
Description