Real time monitor
Refer to page 117 for details of the monitor description.
∗1 Use Pr. 37 to set 1 increments, and use Pr. 144 to set 0.01Hz increments. (Refer to page 115 for Pr. 37 and Pr. 144.)
∗2 Input terminal monitor details (when the terminal is ON: 1, when the terminal is OFF: 0, —: undetermined value)
∗3 Output terminal monitor details (when the terminal is ON: 1, when the terminal is OFF: 0, —: undetermined value)
b15 b0
—————————RHRMRL——STRSTF
b15 b0
——————————ABC————RUN
Register
Description Unit
40201
Rotation speed/Machine speed/
Output frequency
∗1
1/1/0.01Hz
40202 Output current 0.01A
40203 Output voltage 0.1V
40205
Rotation speed setting/Machine
speed/Frequency setting
∗1
1/1/0.01Hz
40208 Converter output voltage 0.1V
40209 Regenerative brake duty 0.1%
40210
Electronic thermal relay function
load factor
0.1%
40211 Output current peak value 0.01A
40212 Converter output voltage peak value 0.1V
40214 Output power 0.01kW
40215 Input terminal status ∗2 —
40216 Output terminal status ∗3 —
40220 Cumulative energization time 1h
40223 Actual operation time 1h
40224 Motor load factor 0.1%
40225 Cumulative power 1kWh
40252 PID set point 0.1%
40253 PID measured value 0.1%
40254 PID deviation 0.1%
40261 Motor thermal load factor 0.1%
40262 Drive unit thermal load factor 0.1%
40263 Cumulative power 2 0.01kWh
40264 PTC thermistor resistance 0.01kΩ
40277
32-bit cumulative power
(lower 16-bit)
1kWh
40278
32-bit cumulative power
(upper 16-bit)
1kWh
40279
32-bit cumulative power
(lower 16-bit)
0.01kW
h
40280
32-bit cumulative power
(upper 16-bit)
0.01kW
h
Register
Description Unit