Ingersoll-Rand EP50-PE Air Compressor User Manual


 
INSTALLATION / HANDLING
19
SSR UP6 40, SSR UP6 50PE, SSR UP6 50PEI, HF50–PE, EP50–PE,
HP50–PE, HXP50–PE
ELECTRICAL DATA – ALL UNITS SSR UP6–40–HA
Standard voltage 200V 230V 380V 460V 575V
PACKAGE
Motor enclosure ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC
Power (nominal) 40HP
Full load current at maximum
pressure
136.0A 128.3A 119.0A 111.5A 71.6A 65.1A 59.5A 56.9A 47.6A 44.7A
Full load current at maximum
pressure with dryer option
123.5A 116.0A 61.7A 58.1A
Starting current FV (STAR) 706 (265) 617 (231) 374 (140) 309 (115) 247 (93)
Starting current FV (STAR)
with dryer option
652 (268) 323 (131)
Starting time FV (STAR) 3–5 Sec (7–10 Sec)
Starts per hour (maximum) 6
ELECTRICAL DATA – FV / Star Delta
Control voltage 120VAC
Minimum fuse rating
See note 1
175A 150A 90A 75A 60A
Minimum fuse rating with dryer
option
See note 1
175A 150A 80A 75A
Minimum wire size AWG
See note 2
4/0 3/0 2 3 4
ELECTRICAL DATA – ALL UNITS SSR 30E–HA
Standard voltage 200V 230V 380V 460V 575V
PACKAGE
Motor enclosure ODP TEFC ODP TEFC ODP TEFC ODP TEFC ODP TEFC
Power (nominal) 30HP
Full load current at maximum
pressure
109.2A 100.9A 95.0A 87.8A 57.5A 53.1A 47.5A 43.9A 38.0A 38.3A
Full load current at maximum
pressure with dryer option
99.5A 92.3A 49.7A 46.1A
Starting current FV (STAR) 567 (212.4) 493.2 (184.8) 298.5 (111.8) 246.6 (92.4) 197.3 (73.9)
Starting current FV (STAR)
with dryer option
516.6 (193.5) 258 (96.7)
Starting time FV (STAR) 3–5 Sec (7–10 Sec)
Starts per hour (maximum) 6
ELECTRICAL DATA – FV / Star Delta
Control voltage 120VAC
Minimum fuse rating
See note 1
150A 125A 125A 125A 75A 75A 60A 60A 50A 50A
Minimum fuse rating with dryer
option
See note 1
150A 150A 75A 75A
Minimum wire size AWG
See note 2
3/0 1/0 3 4 6
http://air.ingersollrand.com