Schneider Electric Altivar 212 Welder User Manual


 
Configuration
S1A53844 01/2011 27
Configuration of the indirect blocks
Configuration
These parameters configure the Modbus functions "Read indirect block (3)", page 34 and "Write indirect block
(16)", page 38.
Access to the parameters
All parameters are accessible in the [COMMUNICATION MENU] COM submenu of [PROGRAMMING
MENU] Programming mode.
Description
Parameters Modbus
address
Adjustment range Default
setting
Valid
after
[Block write data 1] (F870) 2160
16#870
0 [No select]: No selection
1 [Command word 1]
2 [Command word 2]
3 [Frequency Setpoint]
4 [Relay command]: Ouput data on the terminal board
5 [FM command]: Analog output for communication
6 [Speed Setpoint]
0
Power
cycle
[Block write data 2] (F871) 2161
16#871
[Block read data 1] (F875) 2165
16#875
0 [No select]: No selection
1 [Status info]
2 [Freq. out]: Output frequency
3 [Motor current]: Ouput current
4 [Ouput volt]: Ouput voltage
5 [Alarm info]: Alarm information
6 [PID feedback value]
7 [Input term. mon]: Input terminal board monitor
8 [Out term. mon]: Output terminal board monitor
9 [VIA monitor]: VIA terminal board monitor
10 [VIB monitor]: VIB terminal board monitor
11 [Mot speed mon.]: Ouput motor speed monitor
0
Power
cycle
[Block read data 2]
(F876) 2166
16#876
[Block read data 3] (F877) 2167
16#877
[Block read data 4] (F878) 2168
16#878
[Block read data 5] (F879) 2169
16#879