Schneider Electric Altivar 212 Welder User Manual


 
Parameter list
S1A53844 01/2011 49
Examples:
Run forward (CMOd and FMOd configured to serial communication)
FA00 = 16# 0400
Run reverse (CMOd and FMOd configured to serial communication)
FA00 = 16# 0600
Run forward, commands and setpoint from Modbus (irrespective of CMOd and FMOd)
FA00 = 16# C400
Run reverse, commands and setpoint from Modbus (irrespective of CMOd and FMOd)
FA00 = 16# C600
Command word 2 (FA20)
Energy reset (bit 1):
This command is enabled regardless of the command priority selection (bit 15 of common word (FA00)).
It is necessary to reset it after the command is performed.
Over-current stall level change (bit 12):
This command word is enabled only when the communication command is enabled. Set Bit 15 of the
Command word (FA00) to "1" [enabled].
This command word will be disabled is set (value 0), power is turned off or is reset, or factory setting
[Parameter reset] (tYP) is selected.
Bit Function 0 1 Note
0 Reserved - - -
1 Energy reset No reset Reset Input energy (FE76)
Output energy (FE77)
2 to 11 Reserved - - Do not set to "1"
12 Over-current stall level change OC stall 1 OC stall 2 OC1 (F601), OC2 (F185)
13 to 15 Reserved - - Do not set to "1"