Schneider Electric Altivar 212 Welder User Manual


 
Parameter list
S1A53844 01/2011 47
Power and energy
Maintenance
I/O values
Trip and alarm codes
Parameter Modbus
address
Unit Description
Input power (
FE29)
65065 16#FE29 kW Value before trip
Output power (
FE30)
65072 16#FE30 kW Value before trip
Input energy (
FE76)
65142 16#FE76 kWh -
Output energys (
FE77)
65143 16#FE77 kWh -
Parameter Modbus
address
Unit Description
Motor load (
FE26)
65062 16#FE26 % Value before trip
Inverter load (
FE27)
65063 16#FE27 % Value before trip
Cumulative run time (
FE14)
65044 16#FE14 h -
Cumulative power on time (
FE80)
65152 16#FE80 h -
Parameter Modbus
address
Description
Digital inputs status
Fd06
64774 16#Fd06 Current value
Digital outputs status
Fd07
64775 16#Fd07 Current value
Digital inputs status at last trip
FE06
65030 16#FE06 Value before trip
Digital outputs status at last trip
FE07
65030 16#FE07 Value before trip
Analog input VIA value
FE35
65077 16#FE35 -
Analog input VIB value
FE36
65078 16#FE36 -
Parameter Modbus
address
Description
Trip code
FC90
64656 16#FC90 -
Alarm code
FC91
64657 16#FC91 -
Alarm of run
FE79
65145 16#FE79 -
Latest trip code
FE10
65040 16#FE10 -
2nd previous trip code
FE11
65041 16#FE11 -
3rd previous trip code
FE12
65042 16#FE12 -
4th previous trip code
FE13
65043 16#FE13 -