Schneider Electric Altivar 212 Welder User Manual


 
Parameter list
S1A53844 01/2011 51
Status
Status word (FE0I Fd01)
Status immediately before the occurrence of a trip: [Communication Number] (FE01)
Current status: [Communication Number] (Fd01)
Bit Specifications 0 1 Remarks
0 FL state Not active Active
1 Drive state Not tripped Tripped Trip statuses include rtry
and trip retention status.
2 Alarm No alarm Alarm issued
3 MOFF Normal MOFF Main circuit undervoltage
alarm.
4 Motor section (1 or 2)
(THR 2 selection)
Motor 1 (THR 1) Motor 2 (THR 2) THR1: PT=set value, uL, ub,
Thr
THR2: PT=0, F170, F172,
F173
5 PI control OFF PI control permitted PI control prohibited
6 Acceleration/deceleration
pattern selection (1 or 2)
Acceleration/deceleration
pattern 1 (AD 1)
Acceleration/deceleration
pattern 2 (AD 2)
AD1: ACC, DEC,
AD2: F500, F501
7 DC braking OFF Forced DC braking
8Reserved - -
9 Forward/reverse run Forward run Reverse run
10 Run/stop Stop Run
11 Coast stop (ST=OFF) ST=ON ST=OFF
12 Emergency stop Not emergency stop
status
Emergency stop status
13 Standby ST=ON Start-up process Standby Standby: Initialization
completed, not detected fault
stop status, not alarm stop
status (MOFF, LL forced stop
or forced stop due to a
momentary power OFF),
ST=ON, and RUN=ON
14 Standby Start-up process Standby Standby: Initialization
completed, not detected fault
stop status, and not alarm stop
status (MOFF, LL forced stop
or forced stop due to a
momentary power OFF)
15 Local/Remote status Remote Local Command is "FA08"