Parameter list
52 S1A53844 01/2011
Status word 2 (FE42 Fd42)
Status 2 immediately before the occurrence of a trip: Communication Number FE42
Current status 2: Communication Number FD42
Status word 3 (FE49 Fd49)
Status 3 immediately before the occurrence of a trip: Communication Number FE49
Current status 3: Communication Number FD49
Command mode status (FE45)
This parameter monitors the source of the commands.
Setpoint mode status (FE46)
This parameter monitors the source of the setpoint.
Bit Function 0 1 Remarks
0 Reserved - -
1 Electric Power Counting (FE76,FE77) status Counting Resetting
2 to 7 Reserved - -
8 Acceleration/deceleration pattern selection1 Acc/Dec 1 Acc/Dec 2
9 to 11 Reserved - -
12 Over-current stall level change OC stall 1 OC stall 2 OC1: F601, OC2: F185
13 to 15 Reserved - -
Bit Function 0 1 Remarks
0 RY terminal output hold OFF Holding
1 to 11 Reserved - -
12 RCH OFF ON F102
13 RCHF OFF ON F101, F102
14 and 15 Reserved - -
Data Function
0 Terminal board
1 Operation panel
2 Serial communication
Data Function
0-
1VIA
2VIB
3 Operation panel
4 Serial communications
5 TB up down frequency
6-
255 Preset speed operation