Parameter list
S1A53844 01/2011 45
List of control parameters
These parameters are only in the RAM and not in the EEPROM, they return to initial values when the power
is turned off, after the drive has been reseted, or when factory setting is done.
Commands from serial communication
Setpoints from serial communication
Outputs control from serial communication
Parameter
description
Modbus
address
Range Min.
setting unit
Initial
value
Write during
operation
EEPROM
Command word 1 (FA00)
from serial communication
64000
16#FA00
0 to 65535 - 0 Yes None
Command word 2 (FA20)
from serial communication
64032
16#FA20
0 to 65535 - 0 Yes None
Parameter
description
Modbus
address
Range Min.
setting unit
Initial
value
Write during
operation
EEPROM
Frequency reference from serial comm.
(FA01)
64001
16#FA01
0 to Max.
frequency
(FH)
0.01 Hz 0 Yes None
Speed reference from network (FA13) 64019
16#FA13
0 to 24000
1 min
-1
(1 rpm)
0 Yes None
Parameter
description
Modbus
address
Range Min.
setting unit
Initial
value
Write during
operation
EEPROM
Terminal output data from comm. (FA50) 64080
16#FA50
0 to 255 0 0 Yes None
Analog output data from comm. (FA51) 64081
16#FA51
0 to 1023
(10-bit
resolution)
0 0 Yes None