System Sensor PDRP-1001 Stud Sensor User Manual


 
2. Installation Optional Modules
26
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
Zone Relay Module - 4XZM
Note: The PAR-3 includes one (1) Zone Relay Module (4XZM).
Relay #1 through #4 on this module will activate with outputs #1 through #4.
For non-latching (silenceable) relay operation, cut the jumper “LATCH”. If this jumper is left intact, the
relays will latch upon activation. To disconnect relays entirely, slide the disable switch to the right.
Note: If any dry contacts are to be used as nonpower-limited circuits, write this on the Protected Premises Unit label,
located on the door of the control panel.
Figure 16 Wiring the Zone Relay Module
The wiring of this module must follow the requirements specified under "Power-limited Wiring
Requirements" on page 17.
If this module is used to drive both nonpower-limited and power-limited circuits, skip one set of
dry contacts to maintain the required separation between circuit types.
If this module is used to drive both nonpower-limited and power-limited relays that are next to each
other, refer to the figure below which shows the one allowable arrangement.
Figure 17 Mixing Power-Limited and Nonpower-Limited Circuits
TB1
LATCH
DISABLE
J2
Disable Switch“Latch” Jumper
4XZMF.cdr
Power-Limited
Circuit
Nonpower-Limited
Circuit
MS44--4xzmf1.cdr
No Connection