1. Product Description
Overview
The PDRP-1001 Series Deluge - Preaction Control System has been designed as a control center for use
in single- and dual-hazard deluge and preaction applications. The panel is a feature-packed control unit
suitable to perform detection and control functions associated with the release of water-based fire
protection systems. The panel is designed for maximum reliability with 100% solid state circuitry and
isolated relay contacts for outside interfacing and features programmable options to allow on-site
customization of the unit for various operating configurations.
An integral standby battery system, with charger, is provided. In case of commercial AC power
interruption, automatic switchover to the battery system will provide power to the panel for a minimum
of 24 hours.
The control panel is supplied complete with backbox, hinged door, control switches, and indicator LEDs.
The entire unit is housed in a standard sheet-metal enclosure with 1/2 in. (12.7 mm) and 3/4 in. (19.05 mm)
conduit knockouts available.
The PDRP-1001 and PDRP-1001A are 110/120 VAC control panels. The PDRP-1001E is a 220/240 VAC
control panel.
Features
Options
Note: Applications which require the 411UDAC or the NOTI-FIRE 911AC are not FM approved.
Microprocessor-controlled
Alarm and trouble resound
Four Style B/D Initiating Device Circuits
Two Style Y/Z Notification Appliance Circuits
Two Style Y Release Circuits
General alarm and trouble relays
Designed for sprinkler standards NFPA 13, 15 & 16.
Disable/enable controls per Initiating Device Circuit
Last Event Recall
Battery/Earth fault supervision
Current protection on all notification circuits
RMS regulated output power, 2.25 amps
7 amp-hour (AH) to 18 AH battery options, up to 90
hours standby
Resettable and nonresettable regulated power
outputs
Extensive transient protection
Watchdog timer to supervise microprocessor
Output circuits protected against false activations
Slide-in zone identification labels
Steel cabinet 14.5” (36.83cm) wide by 16.00”
(40.64cm) high by 4.75” (12.07cm) deep
Dual Hazard operation
Municipal Box output
Adjustable discharge timer
4XTM Transmitter Module - Complies with NFPA
72 Auxiliary and Remote Station Protective
Signaling systems
4XZM Zone Relay Module for zone/function relays
RZA-4X Supervised remote annunciator (requires
4XLM Interface Module)
411UDAC or NOTI•FIRE 911AC Digital
Communicator - Complies with NFPA 72 Central
Station and Remote Station Protective Signaling
systems
4XMM Volt/Amp Meter Module
Cross-zone option
Dead-front dress panel option (DP-4X)
(Required for Canadian applications)
Trim ring for flush mount between 16 in. (40.64 cm)
center studs (TR-4XR)