System Sensor PDRP-1001 Stud Sensor User Manual


 
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
39
Appendix B: Compatible Devices
Two-wire Smoke Detectors, UL Listed
Use the two-wire detectors listed below.
Table 3 Two-wire Smoke Detectors
Detector
Model
Identifier Type
Base
Model
Identifier
Standby
Current
(mA)
Detectors
per Zone
System Sensor 1400 A Ionization n/a n/a 0.10 20
System Sensor 1451 A Ionization B401/B401B/
B406B
A 0.12 15/15/1
System Sensor 1851DH A Ionization DH1851DC A 0.12 15
System Sensor 2400 A Photoelectric n/a n/a 0.12 15
System Sensor 2400AIT A Photo/
Isolated
Thermal/Horn
n/a n/a 0.12 15
System Sensor 2400AT A Photo/
Thermal/Horn
n/a n/a 0.12 15
System Sensor 2400TH A Photo/
Thermal
n/a n/a 0.12 15
System Sensor 2451 A Photoelectric B401/B401B/
B406B
A 0.12 15/15/1
System Sensor 2451TH A Photo/
Thermal
B401/B401B/
B406B
A 0.12 15/15/1
System Sensor 2851DH A Photoelectric DH2851DC A 0.12 15
System Sensor 1451DH A Ionization DH400 A 0.12 15
System Sensor 2451 A Photoelectric DH400 A 0.12 15
System Sensor 2300T A Photo/
Thermal
n/a n/a 0.12 15
System Sensor 1800 A Ionization n/a n/a 0.12 n/a
System Sensor 1851B A Ionization B101B A 0.12 n/a
System Sensor 1851B A Ionization B107B A 0.12 n/a
System Sensor 2800 A Photoelectric n/a n/a 0.12 n/a
System Sensor 2800TH A Photo/
Thermal
n/a n/a 0.12 n/a
System Sensor 2851B A Photoelectric B101B A 0.12 n/a
System Sensor 2851B A Photoelectric B107B A 0.12 n/a
System Sensor 2851BTH A Photo/
Thermal
B101B A 0.12 n/a
System Sensor 2851BTH A Photo/
Thermal
B107B A 0.12 n/a
System Sensor 1151 A Ionization B401/
B110LP/
B116LP
A 0.12 15/15/1
System Sensor 2151 A Photoelectric B401/
B110LP/
B116LP
A 0.12 15/15/1