Modbus Memory Map
489
Communications Guide
http://www.GEindustrial.com/multilin
17
GE Multilin
0643 RTD #4 Maximum Temperature (Fahrenheit) –52 to 251 1 °F F4 –52
0644 RTD #5 Maximum Temperature (Fahrenheit) –52 to 251 1 °F F4 –52
0645 RTD #6 Maximum Temperature (Fahrenheit) –52 to 251 1 °F F4 –52
0646 RTD #7 Maximum Temperature (Fahrenheit) –52 to 251 1 °F F4 –52
0647 RTD #8 Maximum Temperature (Fahrenheit) –52 to 251 1 °F F4 –52
0648 RTD #9 Maximum Temperature (Fahrenheit) –52 to 251 1 °F F4 –52
0649 RTD #10 Maximum Temperature (Fahrenheit) –52 to 251 1 °F F4 –52
064A RTD #11 Maximum Temperature (Fahrenheit) –52 to 251 1 °F F4 –52
064B RTD #12 Maximum Temperature (Fahrenheit) –52 to 251 1 °F F4 –52
LEARNED DATA / ANALOG IN MIN/MAX
0700 Analog Input 1 Minimum –50000 to 50000 1 Units F12 0
0702 Analog Input 1 Maximum –50000 to 50000 1 Units F12 0
0704 Analog Input 2 Minimum –50000 to 50000 1 Units F12 0
0706 Analog Input 2 Maximum –50000 to 50000 1 Units F12 0
0708 Analog Input 3 Minimum –50000 to 50000 1 Units F12 0
070A Analog Input 3 Maximum –50000 to 50000 1 Units F12 0
070C Analog Input 4 Minimum –50000 to 50000 1 Units F12 0
070E Analog Input 4 Maximum –50000 to 50000 1 Units F12 0
MAINTENANCE / TRIP COUNTERS
077F Trip Counters Last Cleared (Date) N/A N/A N/A F18 N/A
0781 Total Number of Trips 0 to 50000 1 F1 0
0782 Digital Input Trips 0 to 50000 1 F1 0
0783 Sequential Trips 0 to 50000 1 F1 0
0784 Field-Breaker Discrepancy Trips 0 to 50000 1 F1 0
0785 Tachometer Trips 0 to 50000 1 F1 0
0786 Offline Overcurrent Trips 0 to 50000 1 F1 0
0787 Phase Overcurrent Trips 0 to 50000 1 F1 0
0788 Negative Sequence Overcurrent Trips 0 to 50000 1 F1 0
0789 Ground Overcurrent Trips 0 to 50000 1 F1 0
078A Phase Differential Trips 0 to 50000 1 F1 0
078B Undervoltage Trips 0 to 50000 1 F1 0
078C Overvoltage Trips 0 to 50000 1 F1 0
078D Volts/Hertz Trips 0 to 50000 1 F1 0
078E Phase Reversal Trips 0 to 50000 1 F1 0
078F Underfrequency Trips 0 to 50000 1 F1 0
0790 Overfrequency Trips 0 to 50000 1 F1 0
0791 Neutral Overvoltage (Fundamental) Trips 0 to 50000 1 F1 0
0792 Neutral Undervoltage (3rd Harmonic) Trips 0 to 50000 1 F1 0
0793 Reactive Power Trips 0 to 50000 1 F1 0
0794 Reverse Power Trips 0 to 50000 1 F1 0
0795 Low Forward Power Trips 0 to 50000 1 F1 0
0796 Stator RTD Trips 0 to 50000 1 F1 0
0797 Bearing RTD Trips 0 to 50000 1 F1 0
0798 Other RTD Trips 0 to 50000 1 F1 0
0799 Ambient RTD Trips 0 to 50000 1 F1 0
079A Thermal Model Trips 0 to 50000 1 F1 0
079B Inadvertent Energization Trips 0 to 50000 1 F1 0
079C Analog Input 1 Trips 0 to 50000 1 F1 0
079D Analog Input 2 Trips 0 to 50000 1 F1 0
079E Analog Input 3 Trips 0 to 50000 1 F1 0
079F Analog Input 4 Trips 0 to 50000 1 F1 0
MAINTENANCE / GENERAL COUNTERS
07A0 Number Of Breaker Operations 0 to 50000 1 F1 0
Table 1: 489 Memory Map (Sheet 7 of 29)
ADDR NAME RANGE STEP UNITS FORMAT DEFAULT
1, 2, 3 See Table footnotes on page 39