GE 1601-0149-A2 Dust Collector User Manual


 
Modbus Memory Map489
Communications Guide
http://www.GEindustrial.com/multilin
30
GE Multilin
2428 RTD #1 Trip Temperature 1 to 250 1 °C F1 155
2429 RTD #1 Name 0 to 8 1 F22 _
RTD TEMPERATURE / RTD #2
2460 RTD #2 Application 0 to 4 1 F121 1
2461 RTD #2 Alarm 0 to 2 1 F115 0
2462 Assign Alarm Relays (2-5) 1 to 4 1 F50 16
2463 RTD #2 Alarm Temperature 1 to 250 1 °C F1 130
2464 RTD #2 Alarm Events 0 to 1 1 F105 0
2465 RTD #2 Trip 0 to 2 1 F115 0
2466 RTD #2 Trip Voting 1 to 12 1 F122 2
2467 Assign Trip Relays (1-4) 0 to 3 1 F50 1
2468 RTD #2 Trip Temperature 1 to 250 1 °C F1 155
2469 RTD #2 Name 0 to 8 1 F22 _
RTD TEMPERATURE / RTD #3
24A0 RTD #3 Application 0 to 4 1 F121 1
24A1 RTD #3 Alarm 0 to 2 1 F115 0
24A2 Assign Alarm Relays (2-5) 1 to 4 1 F50 16
24A3 RTD #3 Alarm Temperature 1 to 250 1 °C F1 130
24A4 RTD #3 Alarm Events 0 to 1 1 F105 0
24A5 RTD #3 Trip 0 to 2 1 F115 0
24A6 RTD #3 Trip Voting 1 to 12 1 F122 3
24A7 Assign Trip Relays (1-4) 0 to 3 1 F50 1
24A8 RTD #3 Trip Temperature 1 to 250 1 °C F1 155
24A9 RTD #3 Name 0 to 8 1 F22 _
RTD TEMPERATURE / RTD #4
24E0 RTD #4 Application 0 to 4 1 F121 1
24E1 RTD #4 Alarm 0 to 2 1 F115 0
24E2 Assign Alarm Relays (2-5) 1 to 4 1 F50 16
24E3 RTD #4 Alarm Temperature 1 to 250 1 °C F1 130
24E4 RTD #4 Alarm Events 0 to 1 1 F105 0
24E5 RTD #4 Trip 0 to 2 1 F115 0
24E6 RTD #4 Trip Voting 1 to 12 1 F122 4
24E7 Assign Trip Relays (1-4) 0 to 3 1 F50 1
24E8 RTD #4 Trip Temperature 1 to 250 1 °C F1 155
24E9 RTD #4 Name 0 to 8 1 F22 _
RTD TEMPERATURE / RTD #5
2520 RTD #5 Application 0 to 4 1 F121 1
2521 RTD #5 Alarm 0 to 2 1 F115 0
2522 Assign Alarm Relays (2-5) 1 to 4 1 F50 16
2523 RTD #5 Alarm Temperature 1 to 250 1 °C F1 130
2524 RTD #5 Alarm Events 0 to 1 1 F105 0
2525 RTD #5 Trip 0 to 2 1 F115 0
2526 RTD #5 Trip Voting 1 to 12 1 F122 5
2527 Assign Trip Relays (1-4) 0 to 3 1 F50 1
2528 RTD #5 Trip Temperature 1 to 250 1 °C F1 155
2529 RTD #5 Name 0 to 8 1 F22 _
RTD TEMPERATURE / RTD #6
2560 RTD #6 Application 0 to 4 1 F121 1
2561 RTD #6 Alarm 0 to 2 1 F115 0
2562 Assign Alarm Relays (2-5) 1 to 4 1 F50 16
2563 RTD #6 Alarm Temperature 1 to 250 1 °C F1 130
2564 RTD #6 Alarm Events 0 to 1 1 F105 0
2565 RTD #6 Trip 0 to 2 1 F115 0
Table 1: 489 Memory Map (Sheet 20 of 29)
ADDR NAME RANGE STEP UNITS FORMAT DEFAULT
1, 2, 3 See Table footnotes on page 39