GE 1601-0149-A2 Dust Collector User Manual


 
DNP Point Lists 489
Communications Guide
http://www.GEindustrial.com/multilin
49
GE Multilin
DNP Point Lists
Binary Input / Binary
Input Change (Objects
01/02)
The point list for Binary Inputs (Object 01) and Binary Input Change (Object 02) is
shown below:
Table 5: Binary Inputs (Sheet 1 of 4)
Idx Description Class
0 Relay In Service Class 1
1 Trip Condition Active Class 1
2 Alarm Condition Active Class 1
3 Simulation Mode Enabled Class 1
4 Breaker Is Open Class 1
5 Breaker Is Closed Class 1
6 Hot Stator Fault Active Class 1
7 Negative Sequence Fault Active Class 1
8 Ground Fault Active Class 1
9 Loss Of Field Fault Active Class 1
10 VT Failure Detected Class 1
11 Breaker Failure Detected Class 1
12 Relay 1 Trip Operated Class 1
13 Relay 2 Auxiliary Operated Class 1
14 Relay 3 Auxiliary Operated Class 1
15 Relay 4 Auxiliary Operated Class 1
16 Relay 5 Alarm Operated Class 1
17 Relay 6 Service Operated Class 1
18 Setpoint Access Input Closed Class 1
19 Breaker Status Input Closed Class 1
20 Assignable Input 1 Closed Class 1
21 Assignable Input 2 Closed Class 1
22 Assignable Input 3 Closed Class 1
23 Assignable Input 4 Closed Class 1
24 Assignable Input 5 Closed Class 1
25 Assignable Input 6 Closed Class 1
26 Assignable Input 7 Closed Class 1
27 Trip Coil Supervision - Coil
Detected
Class 1
40 Assignable Input 1 Trip Active
or Latched
Class 1
41 Assignable Input 2 Trip Active
or Latched
Class 1
42 Assignable Input 3 Trip Active
or Latched
Class 1
43 Assignable Input 4 Trip Active
or Latched
Class 1
44 Assignable Input 5 Trip Active
or Latched
Class 1
45 Assignable Input 6 Trip Active
or Latched
Class 1
46 Assignable Input 7 Trip Active
or Latched
Class 1
47 Sequential Trip Active or
Latched
Class 1
48 Field-Breaker Discrepancy Trip
Active or Latched
Class 1
49 Tachometer Trip Active or
Latched
Class 1
50 Offline Overcurrent Trip Active
or Latched
Class 1
51 Inadvertent Energization Trip
Active or Latched
Class 1
52 Phase Overcurrent Trip Active
or Latched
Class 1
53 Negative Sequence
Overcurrent Trip Active or
Latched
Class 1
54 Ground Overcurrent Trip Active
or Latched
Class 1
55 Phase Differential Trip Active or
Latched
Class 1
56 Undervoltage Trip Active or
Latched
Class 1
57 Overvoltage Trip Active or
Latched
Class 1
58 Volts/Hertz Trip Active or
Latched
Class 1
59 Phase Reversal Trip Active or
Latched
Class 1
60 Underfrequency Trip Active or
Latched
Class 1
61 Overfrequency Trip Active or
Latched
Class 1
62 Neutral Overvoltage Trip Active
or Latched
Class 1
63 Neutral Undervoltage (Third
Harmonic) Trip Active or
Latched
Class 1
64 Reactive Power Trip Active or
Latched
Class 1
65 Reverse Power Trip Active or
Latched
Class 1
66 Low Fwd Power Trip Active or
Latched
Class 1
67 Thermal Model Trip Active or
Latched
Class 1
68 RTD 1 Trip Active or Latched Class 1
69 RTD 2 Trip Active or Latched Class 1
70 RTD 3 Trip Active or Latched Class 1
71 RTD 4 Trip Active or Latched Class 1
72 RTD 5 Trip Active or Latched Class 1
73 RTD 6 Trip Active or Latched Class 1
74 RTD 7 Trip Active or Latched Class 1
75 RTD 8 Trip Active or Latched Class 1
76 RTD 9 Trip Active or Latched Class 1
77 RTD 10 Trip Active or Latched Class 1
78 RTD 11 Trip Active or Latched Class 1
79 RTD 12 Trip Active or Latched Class 1
80 Analog Input 1 Trip Active or
Latched
Class 1
81 Analog Input 2 Trip Active or
Latched
Class 1
Table 5: Binary Inputs (Sheet 2 of 4)
Idx Description Class