GE 1601-0149-A2 Dust Collector User Manual


 
DNP Point Lists
489
Communications Guide
http://www.GEindustrial.com/multilin
50
GE Multilin
Any detected change in the
state of any point assigned to
Class 1 will cause the generation
of an event object.
82 Analog Input 3 Trip Active or
Latched
Class 1
83 Analog Input 4 Trip Active or
Latched
Class 1
84 Loss of Excitation Circle 1 Trip
Active or Latched
Class 1
85 Loss of Excitation Circle 2 Trip
Active or Latched
Class 1
86 Ground Directional Trip Active
or Latched
Class 1
87 High Set Phase Overcurrent
Trip Active or Latched
Class 1
88 Distance Zone 1 Trip Active or
Latched
Class 1
89 Distance Zone 2 Trip Active or
Latched
Class 1
100 Assignable Input 1 Alarm
Active / Latched
Class 1
101 Assignable Input 2 Alarm
Active or Latched
Class 1
102 Assignable Input 3 Alarm
Active or Latched
Class 1
103 Assignable Input 4 Alarm
Active or Latched
Class 1
104 Assignable Input 5 Alarm
Active or Latched
Class 1
105 Assignable Input 6 Alarm
Active or Latched
Class 1
106 Assignable Input 7 Alarm
Active / Latched
Class 1
107 Tachometer Alarm Active or
Latched
Class 1
108 Overcurrent Alarm Active or
Latched
Class 1
109 Negative Sequence Alarm
Active or Latched
Class 1
110 Ground Overcurrent Alarm
Active or Latched
Class 1
111 Undervoltage Alarm Active or
Latched
Class 1
112 Overvoltage Alarm Active or
Latched
Class 1
113 Volts/Hertz Alarm Active or
Latched
Class 1
114 Underfreq Alarm Active or
Latched
Class 1
115 Overfrequency Alarm Active or
Latched
Class 1
116 Neutral Overvoltage Alarm
Active or Latched
Class 1
117 Neutral Undervoltage (Third
Harmonic) Alarm Active or
Latched
Class 1
118 Reactive Power Alarm Active or
Latched
Class 1
119 Reverse Power Alarm Active or
Latched
Class 1
120 Low Forward Power Alarm
Active / Latched
Class 1
121 RTD 1 Alarm Active or Latched Class 1
122 RTD 2 Alarm Active or Latched Class 1
123 RTD 3 Alarm Active or Latched Class 1
Table 5: Binary Inputs (Sheet 3 of 4)
Idx Description Class
124 RTD 4 Alarm Active or Latched Class 1
125 RTD 5 Alarm Active or Latched Class 1
126 RTD 6 Alarm Active or Latched Class 1
127 RTD 7 Alarm Active or Latched Class 1
128 RTD 8 Alarm Active or Latched Class 1
129 RTD 9 Alarm Active or Latched Class 1
130 RTD 10 Alarm Active or Latched Class 1
131 RTD 11 Alarm Active or Latched Class 1
132 RTD 12 Alarm Active or Latched Class 1
133 Open Sensor Alarm Active or
Latched
Class 1
134 Short/Low Temp Alarm Active
or Latched
Class 1
135 Thermal Model Alarm Active or
Latched
Class 1
136 Trip Counter Alarm Active or
Latched
Class 1
137 Breaker Failure Alarm Active or
Latched
Class 1
138 Trip Coil Monitor Alarm Active
or Latched
Class 1
139 VTFF Alarm Active or Latched Class 1
140 Current Dmd Alarm Active or
Latched
Class 1
141 MW Demand Alarm Active or
Latched
Class 1
142 Mvar Demand Alarm Active or
Latched
Class 1
143 MVA Alarm Active or Latched Class 1
144 Analog Input 1 Alarm Active or
Latched
Class 1
145 Analog Input 2 Alarm Active or
Latched
Class 1
146 Analog Input 3 Alarm Active or
Latched
Class 1
147 Analog Input 4 Alarm Active or
Latched
Class 1
148 Not Programmed Alarm Active
or Latched
Class 1
149 Simulation Mode Alarm Active
or Latched
Class 1
150 Output Relays Forced Alarm
Active or Latched
Class 1
151 Analog Output Forced Alarm
Active or Latched
Class 1
152 Test Switch Shorted Alarm
Active or Latched
Class 1
153 Ground Directional Alarm
Active or Latched
Class 1
154 IRIG-B Failure Alarm Active or
Latched
Class 1
155 Generator Running Hour Alarm
Active or Latched
Class 1
Table 5: Binary Inputs (Sheet 4 of 4)
Idx Description Class
NOTE