GE 1601-0149-A2 Dust Collector User Manual


 
Modbus Memory Map
489
Communications Guide
http://www.GEindustrial.com/multilin
33
GE Multilin
282A Time to Trip at 3.75 × FLA 5 to 999999 1 s F10 5
282C Time to Trip at 4.00 × FLA 5 to 999999 1 s F10 5
282E Time to Trip at 4.25 × FLA 5 to 999999 1 s F10 5
2830 Time to Trip at 4.50 × FLA 5 to 999999 1 s F10 5
2832 Time to Trip at 4.75 × FLA 5 to 999999 1 s F10 5
2834 Time to Trip at 5.00 × FLA 5 to 999999 1 s F10 5
2836 Time to Trip at 5.50 × FLA 5 to 999999 1 s F10 5
2838 Time to Trip at 6.00 × FLA 5 to 999999 1 s F10 5
283A Time to Trip at 6.50 × FLA 5 to 999999 1 s F10 5
283C Time to Trip at 7.00 × FLA 5 to 999999 1 s F10 5
283E Time to Trip at 7.50 × FLA 5 to 999999 1 s F10 5
2840 Time to Trip at 8.00 × FLA 5 to 999999 1 s F10 5
2842 Time to Trip at 10.0 × FLA 5 to 999999 1 s F10 5
2844 Time to Trip at 15.0 × FLA 5 to 999999 1 s F10 5
2846 Time to Trip at 20.0 × FLA 5 to 999999 1 s F10 5
2848 Minimum Allowable Voltage 70 to 95 1 % F1 80
2849 Stall Current at Minimum Voltage 200 to 1500 1 × FLA F3 480
284A Safe Stall Time at Minimum Voltage 5 to 9999 1 s F2 200
284B Acceleration Intersect at Minimum Voltage 200 to 1500 1 × FLA F3 380
284C Stall Current at 100% Voltage 200 to 1500 1 × FLA F3 600
284D Safe Stall Time at 100% Voltage 5 to 9999 1 s F2 100
284E Acceleration Intersect at 100% Voltage 200 to 1500 1 × FLA F3 500
THERMAL MODEL / THERMAL ELEMENTS
2900 Thermal Model Alarm 0 to 2 1 F115 0
2901 Assign Alarm Relays (2-5) 1 to 4 1 F50 16
2902 Thermal Alarm Level 10 to 100 1 %Used F1 75
2903 Thermal Model Alarm Events 0 to 1 1 F105 0
2904 Thermal Model Trip 0 to 2 1 F115 0
2905 Assign Trip Relays (1-4) 0 to 3 1 F50 1
MONITORING / TRIP COUNTER
2A00 Trip Counter Alarm 0 to 2 1 F115 0
2A01 Assign Alarm Relays (2-5) 1 to 4 1 F50 16
2A02 Trip Counter Alarm Level 1 to 50000 1 Trips F1 25
2A03 Trip Counter Alarm Events 0 to 1 1 F105 0
MONITORING / BREAKER FAILURE
2A20 Breaker Failure Alarm 0 to 2 1 F115 0
2A21 Assign Alarm Relays (2-5) 1 to 4 1 F50 16
2A22 Breaker Failure Level 5 to 2000 1 ×CT F3 100
2A23 Breaker Failure Delay 10 to 1000 10 ms F1 100
2A24 Breaker Failure Alarm Events 0 to 1 1 F105 0
MONITORING / TRIP COIL MONITOR
2A30 Trip Coil Monitor Alarm 0 to 2 1 F115 0
2A31 Assign Alarm Relays (2-5) 1 to 4 1 F50 16
2A32 Trip Coil Monitor Alarm Events 0 to 1 1 F105 0
MONITORING / VT FUSE FAILURE
2A50 VT Fuse Failure Alarm 0 to 2 1 F115 0
2A51 Assign Alarm Relays (2-5) 1 to 4 1 F50 16
2A52 VT Fuse Failure Alarm Events 0 to 1 1 F105 0
MONITORING / CURRENT DEMAND
2A60 Current Demand Period 5 to 90 1 min F1 15
2A61 Current Demand Alarm 0 to 2 1 A F115 0
2A62 Assign Alarm Relays (2-5) 1 to 4 1 A F50 16
2A63 Current Demand Limit 10 to 2000 1 × FLA F14 125
Table 1: 489 Memory Map (Sheet 23 of 29)
ADDR NAME RANGE STEP UNITS FORMAT DEFAULT
1, 2, 3 See Table footnotes on page 39