1 - 21
1.3.1 Example of operation in basic display mode ("b037" = "04" [factory setting])
- Only basic parameters can be displayed in basic display mode. (All parameters in monitor mode,
four parameters in function mode, or 20 parameters in extended function mode)
- Other parameters are not displayed. To display all parameters, select the full display mode ("b037" =
"00").
<Displayable parameters and sequence of display>
Note:
If a desired parameter is not displayed, check
the setting of function "b037" (function code
display restriction). To display all parameters,
specify "00" for "b037".
No. Display code Item
1 d001 to d104 Monitor display
2 F001 Output frequency setting
3 F002 Acceleration (1) time setting
4 F003 Deceleration (1) time setting
5 F004 Operation direction setting
6 A001 Frequency source setting
7 A002 Run command source setting
8 A003 Base frequency setting
9 A004 Maximum frequency setting
10 A005 [AT] selection
11 A020 Multispeed frequency setting
12 A021 Multispeed 1 setting
13 A022 Multispeed 2 setting
14 A023 Multispeed 3 setting
15 A044 1st control method
16 A045 V/f gain setting
17 A085 Operation mode selection
18 b001 Selection of restart mode
19 b002 Allowable under-voltage power failure time
20 b008 Retry-after-trip selection
21 b011 Retry wait time after trip
22 b037 Function code display restriction
23 b083 Carrier frequency setting
24 b084 Initialization mode selection
25 b130
Selection of overvoltage suppression
function
26 b131 Setting of overvoltage suppression level
27 C021 Setting of intelligent output terminal 11
28 C022 Setting of intelligent output terminal 12
29 C036 Alarm relay active state