3.2 Function Modes
No.
Function name Function code Range of data
5 Function for factory adjustment
C170-C194 Change inhibited
6 Region code for inverter C195 JP (intended for Japan)
7 Capacity code for inverter C196 0.2 to 55.0 (kW)
8 Voltage class code for inverter C197 200 (200 V class) or 400 (400 V class)
9 Inverter mode C198 00(SJ700)
3.3 How To Reference the Data Area (d105) Corresponding to Trip History
In the data area you can directly reference the factors (determined by the gate array) of the past six trips. Do not
change the value set as "C172".
(1) Specify "FFFF" for "C170".
(2) Specify "A56A" for "C171".
(3) Reference the data of "C172". Record the last two digits of the data. (The range of data is "**00" to "**05".)
(4) Specify one of the values listed in the table below for "C171" according to the target trip history data and the value
of "C172".
Value of "C172" Target
history
data
**00 **01 **02 **03 **04 **05
d081 A56E A582 A596 A5AA A5BE A5D2
d082 A5D2 A56E A582 A596 A5AA A5BE
d083 A5BE A5D2 A56E A582 A596 A5AA
d084 A5AA A5BE A5D2 A56E A582 A596
d085 A596 A5AA A5BE A5D2 A56E A582
d086 A582 A596 A5AA A5BE A5D2 A56E
Example 1: Referencing the history data of "d083" when "C172" is "**02"
(1) As shown in the above table, the data of "d083" is "A56E" when "C172" is "**02".
(2) Specify "A56E" for "C171".
(5) Reference the value displayed as "C172". The first two digits of the 4-digit value displayed correspond to the value
of "d105".
Example 2:
When the value of "C172" is "08**", the trip factor is overvoltage protection because bit 3 is "1".
Code of the trip factor determined by gate array